Honeywell XYR 5000 LINE manual Technical Specifications

Models: XYR 5000 LINE

1 49
Download 49 pages 15.75 Kb
Page 41
Image 41

7 Technical Specifications

Power Characteristics

10VDC-30VDC, 24 VDC @ 200mA typical

RF Characteristics

902 MHz – 928 MHz Frequency Hopping Spread Spectrum (FHSS), FCC certified ISM license-free band

Up to 3000’ range to Transmitters with clear line of sight; 500’ to 1000’ range with obstructions

The RF module in each Transmitter is individually tested and calibrated over the full temperature range to ensure reliable wireless operation

Output Options

RS-485 digital communications with conversion to RS-232 or USB for interface with PC or server and WMT (WMT) (optional)

Serial Modbus RTU (Binary) over RS-485

Modbus over TCP/IP (via optional converter)

Physical Characteristic

Baked enamel explosion-proof, weather-proof and corrosion-proof housing

Electromagnetic Compatibility

(CE Compliance)

Operates within specification in fields from 80 to 1,000 MHz with field strengths to 10 V/m. Meets EN 50082-1 general immunity standard and EN 55011 compatibility emissions standard

Industrial Certification

Rated for industrial use FM rated: -40°F to 185°F(-40°C to 85°C) CSA Rated: -40°F to 104°F(-40°C to 40°C)

FM Approved as explosion-proof (XP) for Class I, Division 1, Groups B,C,&D, T6; as dust ignition-proof for Class II/III, Division 1, Groups E, F, &G, T6; indoor and outdoor (Type 4X) hazardous (classified) locations.

CSA Approved as explosion-proof (XP) for Class I, Division 1, Groups B,C,&D, T6; as dust ignition-proof for Class II/III, Division 1, Groups E, F, &G, T6; indoor and outdoor (Type 4X) hazardous (classified) locations.

NEMA 4X explosion-proof housing

34

Page 41
Image 41
Honeywell XYR 5000 LINE manual Technical Specifications