Honeywell XYR 5000 LINE manual Wiring the RS-485/232 Converter to the Base Radio

Models: XYR 5000 LINE

1 49
Download 49 pages 15.75 Kb
Page 17
Image 17

software may require the use of an RS-485 to RS-232 converter, as most PCs cannot be wired directly to RS-485.

To wire the RS-485 cable to the Base Radio we recommend using a 22AWG twisted pair shielded wire. Place one of the twisted pair wires in the “A” (Tx+/Rx+) slot of the same terminal block as the power supply wires, and the other wire in the “B” (Tx-/RX-) slot of the terminal block as shown below in Figure 3-5.

Figure 3-5 Wiring RS-485 to the Base Radio

RS-485 may be wired in-line (in series) to multiple Base Radios. This is called “daisy- chaining”. Only Base Radios using Modbus RS-485 output can be daisy-chained. See Section 3.2.6. Note that Base Radios daisy-chained must be set to different RF Channels to communicate properly on the same wire.

3.2.4 Wiring the RS-485/232 Converter to the Base Radio

Honeywell offers an optically isolated, surge protected, DIN Rail mountable RS-485/232 converter, AIC #. Because there are many RS-485/232 Converters available, please see your converter’s instruction manual for details as this section will only discuss the wiring of the B&B 485LDRC9 converter.

The Base Radio communicates via a RS-485 half-duplex differential signal with A being Tx+/Rx+ and B being Tx-/Rx-. To properly wire the Base Radio to the 485LDRC9, you should follow Figure 3-6.

B ase R adio

485LD R C 9

C onverter

 

 

 

A

 

 

H

(T D B )

 

 

B

 

 

G

(T D A )

 

 

 

 

 

 

 

 

Figure 3-6 Base Radio to RS-232 Converter Wiring Diagram

10

Page 17
Image 17
Honeywell XYR 5000 LINE manual Wiring the RS-485/232 Converter to the Base Radio, Wiring RS-485 to the Base Radio