Installation and Operations Manual
Parameters
|
|
| Menu/User | Possible | Default Settings | |||
Label | Characteristic | Description |
|
|
| |||
Low |
| High | ||||||
Level | Settings | Medium | ||||||
|
|
| ||||||
|
|
|
|
| Temp. | Temp. | Temp. | |
|
|
|
|
|
|
|
| |
Regulation |
|
|
|
|
|
| ||
SEt | Set Point |
|
| LS ~ US | 34 | 38 | ||
|
| (0,1 ÷ 25,5°C / 1÷255 °F) Intervention |
|
|
|
|
| |
|
| differential for set point. Compressor |
|
|
|
|
| |
Hy | Differential | Cut IN is Set Point + differential (Hy). | Pr1 | 1~ 45 | 3 | 3 | 3 | |
|
| Compressor Cut OUT is when the |
|
|
|
|
| |
|
| temperature reaches the set point |
|
|
|
|
| |
LS | Minimum set point | (- | Pr2 | 25 | 33 | |||
|
| minimum value for the set point.. |
|
|
|
|
| |
US | Maximum set point | (SET÷110°C/ SET÷230°F). Set the | Pr2 | SET ~ 302F | 37 | 40 | 45 | |
maximum value for set point. | ||||||||
| Thermostat probe |
|
|
|
|
| ||
Ot | to adjust possible offset of the | Pr2 | 0 | 0 | 0 | |||
calibration | ||||||||
| thermostat probe |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
| (0÷255min) This function is |
|
|
|
|
| |
| Outputs activation | enabled at the initial start up of the |
| 0 ~ 255 |
|
|
| |
OdS | instrument and inhibits any output | Pr2 | 0 | 0 | 0 | |||
delay at start up | minutes | |||||||
| activation for the period of time set in |
|
|
|
| |||
|
|
|
|
|
|
| ||
|
| the parameter |
|
|
|
|
| |
| (0÷50 min) minimum interval |
|
|
|
|
| ||
AC | between the compressor stop and | Pr2 | 0 ~ 50 minutes | 4 | 4 | 4 | ||
delay | ||||||||
| the following restart |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
| Compressor OFF | (0÷255 min) time during which the |
| 0 ~ 255 |
|
|
| |
| compressor is OFF in case of faulty | Pr2 |
|
|
| |||
COF | time with faulty | 6 | 6 | 6 | ||||
thermostat probe. With COF=0 | minutes | |||||||
| probe |
|
|
|
| |||
| compressor is always active |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
Display |
|
|
|
|
|
|
| |
|
| °C=Celsius; °F=Fahrenheit. WARNING: |
|
|
|
|
| |
|
| When the measurement unit is |
| °C = Celsius |
|
|
| |
CF | Temperature | changed the SET point and the values | Pr2 | °F | °F | °F | ||
measurement unit | of the parameters Hy, LS, US, Ot, ALU | °F =Fahrenheit | ||||||
|
|
|
|
| ||||
|
| and ALL have to be checked and |
|
|
|
|
| |
|
| modified if necessary |
|
|
|
|
| |
Defrost |
|
|
|
|
|
|
| |
|
|
|
| EL = electric |
|
|
| |
tdF | Defrost type | EL = electrical heater; in = hot gas | Pr2 | defrost / in = | EL | EL | EL | |
|
|
|
| hot gas defrost |
|
|
| |
|
|
|
|
|
|
| ||
dtE | Defrost termination | when EdF=Pb) sets the temperature | Pr1 | 65 | 65 | 38 | ||
temperature | measured by the evaporator probe, | |||||||
|
|
|
|
|
| |||
|
| which causes the end of defrost |
|
|
|
|
| |
| Interval between | (0÷120h) Determines the time |
|
|
|
|
| |
IdF | interval between the beginning of | Pr1 | 0 ~ 120 hours | 6 | 6 | 6 | ||
defrost cycles | ||||||||
| two defrost cycles |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
| (0÷255min) When P2P = n, (not |
|
|
|
|
| |
| (Maximum) length | evaporator probe: timed defrost) it |
| 0 ~ 255 |
|
|
| |
MdF | sets the defrost duration, when P2P = | Pr2 | 40 | 40 | 60 | |||
for defrost | minutes | |||||||
| y (defrost end based on temperature) |
|
|
|
| |||
|
|
|
|
|
|
| ||
|
| it sets the maximum length for defrost |
|
|
|
|
| |
|
| (0÷120 min) time interval between |
|
|
|
|
| |
|
| reaching defrost termination |
|
|
|
|
| |
|
| temperature and the restoring of the |
| 0 ~ 255 |
|
|
| |
Fdt | Drip time | control’s normal operation. This time | Pr1 | 2 | 2 | 0 | ||
minutes | ||||||||
|
| allows the evaporator to eliminate |
|
|
|
| ||
|
|
|
|
|
|
| ||
|
| water drops that might have formed |
|
|
|
|
| |
|
| due to defrost |
|
|
|
|
| |
|
|
|
|
|
|
|
| |
10 |
|
|
|
|
|
|
|