Nortel Networks 8010co manual Powering off the system

Page 64

64Chapter 2 Installation

4Verify the following LEDs on the 8010co chassis:

The (green) power supply LEDs for each power supply in both the upper and lower chassis are on.

(If any of the power supply LEDs are not on, replace the power supply.)

The chassis fans are powering up.

If any of the previous steps indicate a problem with the installation, do the following:

1Set the switches for all power supplies in the upper and lower chassis to the off position (O = Off).

2Set the six circuit breakers on the BIP front panel to the off position (O = Off).

3Check that all cables are installed properly, and that all power supplies are firmly seated in their bays.

4Set the six circuit breakers on the BIP front panel to the on position ( = On).

5Set the switches for all power supplies in the upper and lower chassis to the on position ( = On).

6Proceed to “Verifying the LEDs” on page 63.

If the problem persists, go to Chapter 3, “Problem solving,” on page 67.

Powering off the system

To power off the system:

1Set the switches for all power supplies in the upper and lower chassis to the off position (O = Off).

You can access the power supply switches with the bezels installed.

2Set the six circuit breakers on the BIP front panel to the off position (O = Off).

3Turn off the input feed power at the DC power source.

Warning: Ensure the DC power source is off or disconnected. You may need to switch a circuit breaker off or turn off power at the DC input source. Be sure that the DC input source power is locked out and tagged.

312755-G Rev 00

Image 64
Contents Part No -G Rev May Great America Parkway Santa Clara, CA Copyright 2006 Nortel Networks. All Rights Reserved TrademarksStatement of conditions International regulatory statements of conformityCE marking statement Europe only Vcci statement Japan/Nippon onlyNortel Inc. software license agreement EN 60 950 statementGeneral Rev Contents Contents RevIndex Contents Rev Figures Rack grounding strip example Tables Tables Rev Preface Before you beginHow to get Help Text conventionsGetting Help from the Nortel Web site PrefaceGetting Help over the phone from a Nortel Solutions Center Getting Help through a Nortel distributor or resellerPreface Rev Chapter Overview Physical descriptionShelf circuit breakers upper and lower shelves Front panelOverview Shelf circuit breakers Alarm module display panel Alarm module display LEDsMajor Back panel Shelf alarm connectors upper and lower shelvesFront panel locking screws Shelf alarm connections upper and lower shelves Central office alarms Configuring multiple BIPs to aggregate office alarmsPower terminal block Configuring standalone BIPs to report alarm status1 3 2 1 3 2 1 a 1 a 2 B 1 B Power and grounding example Accessing the alarm module Opening the front panelAccessing the alarm module Configuration example 8010co chassis configuration with BIP optionChapter Installation Preparing to install the breaker interface panelShipment contents DC power requirements Additional equipmentMounting hardware DC input electrical requirementsInstalling the breaker interface panel Installing the hardwareRemoving the plastic back cover from the BIP Connecting cables to the chassis power supplies Removing the 8010co chassis bottom 312096-A bezel Location of power supplies Loosening the power supply retaining screws +DC -DC Power supply cables Attaching the positive lead +DC -DC Replacing the power supply Routing power supply cables to the BIP Labeling cables for the BIPConnecting the ground cables to the rack grounding strip Rack grounding strip exampleConnecting the power supply cables to the BIP Attaching power supply cable leads to the BIPLocate the BIP ground cable see on Attaching the BIP ground cable Connecting DC input power feeds to the BIP B feed example Single chassis and dual chassis input optionsLocating the a and B -48 VDC input feeds Connecting the a and B -48 VDC input feeds to the BIP 1 Connecting the a and B -48 VDC input feeds to the BIP 2 Connecting the A/B input feed returns 1 Go to the next section, Replacing covers on Replacing covers Replacing the plastic back cover on the BIPGo to the next section, Installing shelf alarm cables on Installing shelf alarm cables Installing shelf alarm cablesVerifying the installation Initial power-up Verifying the LEDsPowering off the system Installation Installation Rev Chapter Problem solving Problem solving Interpreting the LEDsOr a problem in circuits that are not essential to Diagnosing and correcting the problem Corrective actions Corrective actionsProblem solving Corrective actions Appendix a Technical specifications EnvironmentalPhysical dimensions Safety agency certificationAppendix a Technical specifications ElectricalShelf alarm connectors J1 and J2 Appendix B BIP external cable pin assignmentsJ1 and J2 shelf alarm connector pin assignments Appendix B BIP external cable pin assignmentsOffice alarm connectors J3 and J4 J3 and J4 high-density 26-pin D-sub connectorJ3 and J4 office alarm connector pin assignments Standalone office alarm connector J5 J5 high-density 26-pin D-sub connectorJ5 standalone office alarm connector pin assignments Index NumbersIndex