Nortel Networks P0607274 0 manual UPS threshold values, Alarm and event reporting

Page 17

Chapter 1 Uninterruptable Power Supply (UPS) Overview 17

UPS threshold values

UPS threshold values are tolerances that define the UPS operational requirements and power delivery capability. The UPS reports the threshold values through the Unified Manager. The following table provides the minimum and maximum UPS threshold values for 110~120 and 220~240 Volt standards. All configuration data is stored in the F:\Program Files\PwerChute\PwrChute.ini file.

 

110 ~ 120 Volt UPS Threshold Values

220 ~ 240 Volt UPS Threshold Values

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

 

 

 

 

 

Line voltage minimum (AC)1

90

120

208

253

Line voltage maximum (AC)2

90

120

208

253

 

 

 

 

 

UPS output voltage (AC)3

106

127

220

240

 

 

 

 

 

Battery voltage (DC)4

16

36

16

36

Output frequency (Hz)5

59

60.25

49

50.25

 

 

 

 

 

UPS load (%)6

0

125

0

125

 

 

 

 

 

Temperature (degr. C)7

-15

45

-15

45

1 Line voltage minimum: The lowest AC input voltage supplied by the power source. This threshold represents the value recorded since you started the user interface module.

2. Line voltage maximum: The highest AC input voltage supplied by the power source. This threshold represents the value recorded since you started the user interface module.

3. UPS Output voltage: The voltage (AC) supplied by the UPS to the equipment supported.

4. Battery voltage: The voltage (DC) supplied by the UPS to the equipment supported during a power outage.

5. Output frequency: The line voltage frequency.

6. UPS load: The amount of battery power drawn by the equipment supported during a recorded interval. The value is represented by the percentage of the total power available in the UPS.

7. Temperature: The internal temperature of the UPS device.

Alarm and event reporting

The BCM software monitors the UPS threshold values and provides event reporting capability to the BCM simple network management protocol (SNMP) trap and alarm reporting systems. The BCM monitors the UPS through the COM port and polls the UPS every 60 seconds. Power supply failure notification is sent to the OAM and alarm subsystem and to the recovery application.

The threshold values relate to the following:

Power: Utility power failure, low battery power for the UPS device. The message advises users to take appropriate action on their BCM. The battery must be recharged for every minute of run time. Appropriate action is to verify the power supply is functional. Alternatively, try to connect to a secondary power supply, possibly switch telephony/data services to alternate location if possible.

Communications: Send a message when communication with the UPS starts. Send a message when communication with the UPS is lost (such as remote UPS shutdown). If communication loss occurs, verify that serial connection is functional or UPS is operational.

UPS Installation and Configuration Guide

Image 17
Contents Part No. P0607274 March 24 North American Regulatory Information SafetyElectromagnetic Compatibility Radio-frequency InterferenceTelecommunication Registration Rights of the Telecommunications Company Telephone Company RegistrationRepairs Canadian Regulations please read carefullyFederal Communications Commission FCC Notice US Regulations please read carefullyImportant Safety Instructions Use Risk of shock Preface P0607274 Display Tips PrefaceAcrobat Reader display setup selections Symbols used in this guideRelated publications How to Get HelpText conventions Preface P0607274 UPS Overview Chapter Uninterruptable Power Supply UPS OverviewBCM Input Power Source BCM and UPS power and control connectionsUPS threshold values Alarm and event reportingUPS Event messages Uninterruptable Power Supply UPS Overview UPS Event messages Operational measurements and accounting UPS default configuration settingsShutdown Uninterruptable Power Supply UPS Overview P0607274 Initialize the serial port Install and Initialize the UPSUPS Configuration screen UPSConsoleToggle ServiceEnable UPSConsoleToggle Enable the console batch file Monitor the UPS Chapter Monitor the Uninterruptable Power SupplyUPS Status Monitor screen Access the UPS Status monitorUPS OMs report Access the UPS OM and log reportsUPS Log file report Access the UPS status reportUPS status report Test the UPSMonitor the Uninterruptable Power Supply