Page 37

3.Verify that the system voltage is above the float voltage if the battery temperature is below 25 degrees C and below the float voltage if the battery temperature is above 25 degrees C.

4.3 Final Inspection:

1.Verify that the interior and exterior of the system is clean and free from debris.

2.Ensure all wires connected and bolts are properly tightened.

3.Ensure the following the User, Service, and Calibration parameters are set properly on the controller (default settings are in parenthesis):

LVD

LVD1 Trip LVD1 Reset

Batt

Batt Disc Thr Batt Float Batt Max Rech Comp Method

4.Verify that the system is functioning correctly with no alarms.

5.Be sure to leave the site as orderly and neat as possible.

Magnum XS 450 Power System –48 VDC User’s Manual

Page 32

Image 37
Contents Magnum XS Vdc Power System User’s Manual Table of Contents Magnum XS 450 Power System -48 VDC User’s Manual Specifications Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information IntroductionMagnum XS 450 Power System -48 VDC User’s Manual How to Use This Manual Mechanical Installation InstallationUnpacking Equipment Room / Location1 Door Clearance Dimensions Ventilation MountingAC Kit with Three Phase Spreader AC Power ConnectionsAC Line AC Neutral Earth Ground AWG AC Kit with Phoenix Terminals OnlyRectifier Shelf and Module Installation Rectifier Shelf Mechanical Rectifier Shelf Serial CommunicationsRectifier AC Input Connections Rectifier Module Installation DC Distribution Module InstallationModule Selection 1 28 Circuit Breaker Module Merlin Gerin 28 Circuit Breaker Module InstallationMerlin Gerin 12 Circuit Breaker Module Installation Circuit Breaker Rating Ordering Number NH2 Fuse Module Installation3 NH2 Fuse Module DC Cabling General InstructionsCircuit Breaker Installation DC Distribution Installation2 Merlin Gerin 28 CB Module Installation Detail C60 C120 Total 4 CB Alarm Interface Board 28 circuit breaker module DC Load Return Module Installation Installing a fuse in the NH2 Fuse ModuleBattery Tray Installation Battery InstallationBattery Installation Battery Disconnect Module Installation1 Battery Cable Connections Negative Battery Cable ConnectionsPositive Battery Cable Connections Battery Return Module InstallationBattery Temperature Probe Installation Monitoring and Relay Output Connections DC System GroundingNetwork Management Card Smart Cable DB9 Connection RJ45 Ethernet ConnectorRelay Output Connections N/C-COpen Closed NO-C NC-C External Alarm Input ConnectionsBattery Visual and Safety Inspection Electrical InstallationCommissioning Pre-Commissioning InspectionCommissioning LVD Test Battery Temperature CompensationCircuit Breaker/ Fuse Test User InputsLVD Final InspectionTechnical Description OperationRectifier Management DC Distribution Battery ManagementExternal Alarm Inputs Input Relays Alarm Outputs Output RelaysCustomer Interface Board System Visual and Safety Inspection Preventive MaintenanceEquipment InspectionTest Battery Current Test System Temperature TestBattery Temperature Test Battery Preventive Maintenance Procedure AC Input DCPM28HN54SH0 Rectifier SpecificationsMechanical EnvironmentalEMC ComplianceAPC Worldwide Customer Support Limited Product Warranty

XS 450 -48 specifications

The American Power Conversion (APC) XS 450 -48 is a reliable and efficient power supply solution designed for critical applications requiring a consistent and stable power source. This solution is particularly beneficial for telecommunications, data centers, and industrial settings where power reliability is paramount.

One of the key features of the XS 450 -48 is its ability to deliver 450 watts of continuous power, ensuring that connected devices receive uninterrupted power supply. Its 48-volt output makes it ideal for telecom requirements, where 48V systems are standard. The unit provides a compact and space-saving design, making it suitable for installation in rack-mounted configurations, optimizing the utilization of valuable real estate in server rooms or equipment racks.

The XS 450 -48 utilizes advanced technologies that enhance its performance and reliability. It is equipped with an active power factor correction (PFC) system that significantly reduces harmonic distortion. This feature not only improves system efficiency but also complies with various regulations concerning power quality. Additionally, the power supply includes built-in over-voltage protection, over-current protection, and short-circuit protection, ensuring that both the power supply and the connected devices are safeguarded against electrical faults.

The unit is designed for high efficiency, often exceeding 90% under full load conditions. This not only reduces energy costs but also minimizes heat generation, contributing to a quieter operation environment. The XS 450 -48's intelligent thermal management system allows it to operate in a range of temperatures, making it highly versatile and adaptable to varying environmental conditions.

Furthermore, monitoring and management capabilities are integrated into the XS 450 -48 with optional external monitoring systems. These systems provide critical insights, allowing technicians to track real-time performance metrics, detect potential issues early on, and perform preventive maintenance.

In conclusion, the American Power Conversion XS 450 -48 stands out as a robust power supply solution that combines reliable performance, advanced protection features, and high efficiency. Its design caters to the specific needs of telecommunications and data centers, making it an indispensable asset for maintaining the uptime and integrity of critical systems. With its range of features and reliability, the XS 450 -48 continues to be a preferred choice among professionals in the field.