2.Check the mechanical integrity of the battery framing, racking, or cabinet. Tighten where necessary.

3.If there is a battery disconnect device fitted, ensure that it is properly connected and protected.

4.Check the general appearance and cleanliness of the battery. Clean if necessary. Use only approved cleaning materials.

5.Visually inspect each cell for the following, and clean and neutralize if necessary. Document discrepancies on Site form accordingly.

a.Cracks.

b.Case leaks.

c.Post-seal leaks.

d.Pressure relief valve leaks (VRLA only).

e.Case swelling (VRLA only).

f.Terminal corrosion and connector corrosion.

6.Check the torque of all battery inter-cell connector in accordance with specifications. Re-torque if necessary (annual only).

7.Measure and record ambient temperature.

6.3Test

System Voltage Test

1.Verify with a voltmeter directly attached to the dc bus that the system voltage is correct.

2.System voltage should also agree with the battery float voltage set up in the battery parameters section. The system may be off because of battery temperature compensation or battery recharging.

Rectifier Current Test

1.Insert voltmeter probe between I+ and common jack on front of each rectifier.

2.Record current for each rectifier using the formula – Voltage X 10 amperes/volt.

3.Rectifier current displayed under Rectifier/Info should agree with the recorded current.

Rectifier Current Share Test

Verify that the highest rectifier current and the lowest rectifier current are within 5 A.

System Current Test

Verify the System current equal to the total of the rectifier currents. System current should equal the total current of the loads as well as any battery current.

Rectifier Alarm Test

1.Verify that all of the rectifiers report RFA Alarm is off.

2.Verify that the battery voltage reading on the voltmeter is negative (-)54.00 Vdc + 0.02 Vdc.

3.Remove 1 rectifier and verify that you get a Minor alarm for Rect 1 of n failure on the controller and the customer remote alarm panel.

4.Remove the second rectifier and verify that you get a Major alarm for Rect 2 of n failure on the controller and the customer remote alarm panel.

Magnum XS 450 Power System –48 VDC User’s Manual

Page 37

Image 42
Contents Magnum XS Vdc Power System User’s Manual Table of Contents Magnum XS 450 Power System -48 VDC User’s Manual Specifications Revision History Revision Date DescriptionSafety First General PrecautionsIntroduction General InformationMagnum XS 450 Power System -48 VDC User’s Manual How to Use This Manual Unpacking Equipment InstallationMechanical Installation Room / Location1 Door Clearance Dimensions Mounting VentilationAC Power Connections AC Kit with Three Phase SpreaderAC Line AC Neutral Earth Ground AC Kit with Phoenix Terminals Only AWGRectifier Shelf and Module Installation Rectifier Shelf Serial Communications Rectifier Shelf MechanicalRectifier AC Input Connections DC Distribution Module Installation Rectifier Module InstallationModule Selection Merlin Gerin 28 Circuit Breaker Module Installation 1 28 Circuit Breaker ModuleMerlin Gerin 12 Circuit Breaker Module Installation NH2 Fuse Module Installation Circuit Breaker Rating Ordering NumberDC Cabling General Instructions 3 NH2 Fuse ModuleDC Distribution Installation Circuit Breaker Installation2 Merlin Gerin 28 CB Module Installation Detail C60 C120 Total 4 CB Alarm Interface Board 28 circuit breaker module Installing a fuse in the NH2 Fuse Module DC Load Return Module InstallationBattery Installation Battery InstallationBattery Tray Installation Battery Disconnect Module InstallationNegative Battery Cable Connections 1 Battery Cable ConnectionsBattery Return Module Installation Positive Battery Cable ConnectionsBattery Temperature Probe Installation DC System Grounding Monitoring and Relay Output ConnectionsNetwork Management Card Relay Output Connections RJ45 Ethernet ConnectorSmart Cable DB9 Connection N/C-CExternal Alarm Input Connections Open Closed NO-C NC-CCommissioning Electrical InstallationBattery Visual and Safety Inspection Pre-Commissioning InspectionCommissioning Circuit Breaker/ Fuse Test Battery Temperature CompensationLVD Test User InputsFinal Inspection LVDOperation Technical DescriptionRectifier Management Battery Management DC DistributionAlarm Outputs Output Relays External Alarm Inputs Input RelaysCustomer Interface Board Equipment Preventive MaintenanceSystem Visual and Safety Inspection InspectionTest System Temperature Test Battery Current TestBattery Temperature Test Battery Preventive Maintenance Procedure Mechanical SpecificationsAC Input DCPM28HN54SH0 Rectifier EnvironmentalCompliance EMCAPC Worldwide Customer Support Limited Product Warranty

XS 450 -48 specifications

The American Power Conversion (APC) XS 450 -48 is a reliable and efficient power supply solution designed for critical applications requiring a consistent and stable power source. This solution is particularly beneficial for telecommunications, data centers, and industrial settings where power reliability is paramount.

One of the key features of the XS 450 -48 is its ability to deliver 450 watts of continuous power, ensuring that connected devices receive uninterrupted power supply. Its 48-volt output makes it ideal for telecom requirements, where 48V systems are standard. The unit provides a compact and space-saving design, making it suitable for installation in rack-mounted configurations, optimizing the utilization of valuable real estate in server rooms or equipment racks.

The XS 450 -48 utilizes advanced technologies that enhance its performance and reliability. It is equipped with an active power factor correction (PFC) system that significantly reduces harmonic distortion. This feature not only improves system efficiency but also complies with various regulations concerning power quality. Additionally, the power supply includes built-in over-voltage protection, over-current protection, and short-circuit protection, ensuring that both the power supply and the connected devices are safeguarded against electrical faults.

The unit is designed for high efficiency, often exceeding 90% under full load conditions. This not only reduces energy costs but also minimizes heat generation, contributing to a quieter operation environment. The XS 450 -48's intelligent thermal management system allows it to operate in a range of temperatures, making it highly versatile and adaptable to varying environmental conditions.

Furthermore, monitoring and management capabilities are integrated into the XS 450 -48 with optional external monitoring systems. These systems provide critical insights, allowing technicians to track real-time performance metrics, detect potential issues early on, and perform preventive maintenance.

In conclusion, the American Power Conversion XS 450 -48 stands out as a robust power supply solution that combines reliable performance, advanced protection features, and high efficiency. Its design caters to the specific needs of telecommunications and data centers, making it an indispensable asset for maintaining the uptime and integrity of critical systems. With its range of features and reliability, the XS 450 -48 continues to be a preferred choice among professionals in the field.