6 Preventive Maintenance

Preventive Maintenance is typically performed on a quarterly basis.

6.1Equipment

1.4 Digit Voltmeter.

2.Clamp-on ampere meter.

3.Standard Insulated tools.

6.2Inspection

Environmental Inspection

1.Ensure the dc system environment is suitable for operation.

2.Ensure that there is sufficient clearance around the system for service.

3.Ensure that there is no sign of damage to the dc system.

4.Contact monitoring personnel or disable system alarms before servicing the unit. This will allow the unit to be serviced without creating false alarms.

System Visual and Safety Inspection

WARNING: Hazardous energy levels are present on bare conductors in the -48 Vdc distribution connection area of the plant. Accidental shorting of distribution conductors can cause arcing and high currents that can cause serious burns or other physical harm. It is recommended that:

Any jewelry, rings or watches be removed while working on this equipment.

Handles of all wrenches, screwdrivers, cutters and pliers are insulated.

1.Ensure that the dc wiring is properly installed, sized, terminated and identified.

2.Ensure that the ac wiring is properly installed, sized, terminated and identified.

3.Ensure that the battery wiring is properly connected to the System.

4.Ensure that the dc output over-current protection devices are adequate for the size of wiring installed.

5.Ensure that the dc Positive is bonded to central office ground (- 48 volt system).

6.Note the resistance of the ground bond.

7.Note any currents flowing in the ground.

8.Record ambient temperature.

9.Verify that the battery polarity is correct.

10.If battery disconnect devices are present, note the following for each device:

a)DC Voltage Rating.

b)DC Current Rating

c)Interrupting Current Rating

Battery Visual and Safety Inspection

1. Check that the battery temperature probe is firmly attached to the battery.

Magnum XS 450 Power System –48 VDC User’s Manual

Page 36

Image 41
Contents Magnum XS Vdc Power System User’s Manual Table of Contents Magnum XS 450 Power System -48 VDC User’s Manual Specifications Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information IntroductionMagnum XS 450 Power System -48 VDC User’s Manual How to Use This Manual Mechanical Installation InstallationUnpacking Equipment Room / Location1 Door Clearance Dimensions Ventilation MountingAC Kit with Three Phase Spreader AC Power ConnectionsAC Line AC Neutral Earth Ground AWG AC Kit with Phoenix Terminals OnlyRectifier Shelf and Module Installation Rectifier AC Input Connections Rectifier Shelf Serial CommunicationsRectifier Shelf Mechanical Module Selection DC Distribution Module InstallationRectifier Module Installation 1 28 Circuit Breaker Module Merlin Gerin 28 Circuit Breaker Module InstallationMerlin Gerin 12 Circuit Breaker Module Installation Circuit Breaker Rating Ordering Number NH2 Fuse Module Installation3 NH2 Fuse Module DC Cabling General InstructionsCircuit Breaker Installation DC Distribution Installation2 Merlin Gerin 28 CB Module Installation Detail C60 C120 Total 4 CB Alarm Interface Board 28 circuit breaker module DC Load Return Module Installation Installing a fuse in the NH2 Fuse ModuleBattery Tray Installation Battery InstallationBattery Installation Battery Disconnect Module Installation1 Battery Cable Connections Negative Battery Cable ConnectionsBattery Temperature Probe Installation Battery Return Module InstallationPositive Battery Cable Connections Network Management Card DC System GroundingMonitoring and Relay Output Connections Smart Cable DB9 Connection RJ45 Ethernet ConnectorRelay Output Connections N/C-COpen Closed NO-C NC-C External Alarm Input ConnectionsBattery Visual and Safety Inspection Electrical InstallationCommissioning Pre-Commissioning InspectionCommissioning LVD Test Battery Temperature CompensationCircuit Breaker/ Fuse Test User InputsLVD Final InspectionRectifier Management OperationTechnical Description DC Distribution Battery ManagementCustomer Interface Board Alarm Outputs Output RelaysExternal Alarm Inputs Input Relays System Visual and Safety Inspection Preventive MaintenanceEquipment InspectionTest Battery Temperature Test System Temperature TestBattery Current Test Battery Preventive Maintenance Procedure AC Input DCPM28HN54SH0 Rectifier SpecificationsMechanical EnvironmentalEMC ComplianceAPC Worldwide Customer Support Limited Product Warranty

XS 450 -48 specifications

The American Power Conversion (APC) XS 450 -48 is a reliable and efficient power supply solution designed for critical applications requiring a consistent and stable power source. This solution is particularly beneficial for telecommunications, data centers, and industrial settings where power reliability is paramount.

One of the key features of the XS 450 -48 is its ability to deliver 450 watts of continuous power, ensuring that connected devices receive uninterrupted power supply. Its 48-volt output makes it ideal for telecom requirements, where 48V systems are standard. The unit provides a compact and space-saving design, making it suitable for installation in rack-mounted configurations, optimizing the utilization of valuable real estate in server rooms or equipment racks.

The XS 450 -48 utilizes advanced technologies that enhance its performance and reliability. It is equipped with an active power factor correction (PFC) system that significantly reduces harmonic distortion. This feature not only improves system efficiency but also complies with various regulations concerning power quality. Additionally, the power supply includes built-in over-voltage protection, over-current protection, and short-circuit protection, ensuring that both the power supply and the connected devices are safeguarded against electrical faults.

The unit is designed for high efficiency, often exceeding 90% under full load conditions. This not only reduces energy costs but also minimizes heat generation, contributing to a quieter operation environment. The XS 450 -48's intelligent thermal management system allows it to operate in a range of temperatures, making it highly versatile and adaptable to varying environmental conditions.

Furthermore, monitoring and management capabilities are integrated into the XS 450 -48 with optional external monitoring systems. These systems provide critical insights, allowing technicians to track real-time performance metrics, detect potential issues early on, and perform preventive maintenance.

In conclusion, the American Power Conversion XS 450 -48 stands out as a robust power supply solution that combines reliable performance, advanced protection features, and high efficiency. Its design caters to the specific needs of telecommunications and data centers, making it an indispensable asset for maintaining the uptime and integrity of critical systems. With its range of features and reliability, the XS 450 -48 continues to be a preferred choice among professionals in the field.