Page 10

Stop, Start & Operating the External Service Bypass Panel

Single Utility

H003

Utility

 

 

 

Load

 

 

Q003

 

H004

 

 

Service

 

 

 

bypass

Q004

 

 

 

switch

 

 

 

 

 

 

 

H002b

H002a

Q001a

Q001b

 

Q002b

Q002a

 

 

DP300E

 

 

DP300E

Dual Utility

 

H003

 

Utility 2

 

Load

 

Q003

 

Service bypass switch

H004

 

Q004

 

H010a

 

 

Q010a

H002a

 

 

 

Utility 1

DP300E

 

Q001a

Q002a

 

H010b

 

 

Q010b

H002b

 

2.7Operating the external service bypass switch, parallel systems

2.7.1Bypassing the parallel UPS system

Action

Point 1-4 can be carried out with any of the parallel systems, however this will switch all systems into bypass operation.

 

 

 

Display shows

1.

Press

on the keyboard

 

 

 

Bypass operation

 

 

 

: NO

2.

Press

or

on the keyboard until

 

 

 

Bypass operation

3.

Press

 

: YES

on the keyboard

4.Press on the keyboard

All systems will transfer to bypass operation

Bypass operation

Do not switch off any of the UPS systems until point 5-8 has been carried out

Lamp indication on bypass panel

 

 

 

 

DP300E

 

 

 

 

 

 

 

 

Q001b

 

 

 

Q002b

 

 

 

WARNING!

If the UPS is out of service for more than 48 hours the connected batteries might be damaged. Refer to total “Switching off“ as described in chapter 2.4.1.

5.Check lamp indication on the bypass panel

6.Turn the external bypass switch (Q003) to position “1“

7.Turn the output switch (Q004) to position “0”

8.Turn all output switches (Q002) to position “0“

9.Open the front door and press the red “OFF” push-button in any of the systems.

The acoustic alarm sounds for 30 secs.* Repeat for (all) other system(s)

The green lamp (H003) above the bypass switch handle (Q003) lights

The green lamp (H004) above the output switch (Q004) and the green lamps (H002) above the output switch handles (Q002) light

H003 turn off

H002 & H004 still lights

H002 & H004 still lights

Display shows

**System OFF**

7OA0004 US rev. 02

10

User Guide Silcon DP300E Series 480V 400-500kVA

Image 10
Contents Silcon DP300E Series 480V 400-500kVA User Guide User Guide Silcon DP300E Series 480V 400-500kVAImportant Safety Instructions Table of Contents General IntroductionIntroduction Display unitStop stand-by Stop Start and Operating the External Service Bypass PanelStart from stand-by Switching off Silcon DP3400E DP3500E Stop for complete power downDisplay shows Start from complete power down Starting up Silcon DP3400E DP3500EAction Display shows Single Utility Dual UtilityBypassing the UPS Lamp indication on bypass panelUPS operation Switching the system from external bypass into normalSingle Utility ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programming346 Programming of system configuration parameters438 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesProgramming parameters for advanced parallel operation Description of settingsParallel programming/operation Programming guideProgramming example Highest Station No Alarm texts conc. parallel operation Parallel operation alarms GeneralOther reasons for parallel operation alarm Reading Out Measurements MeasurementsDescription Alarm stack AlarmsAlarms What To Do Alarm messagesEvents logger Mode CommentsDisplaying the events stack Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Battery Preventive MaintenancePreventive Maintenance FanBattery capacity test Actions Display showsBack-up time Battery monitor testFunctionality of battery test Monitor functionBattery monitor reset Operation of the battery monitorBattery monitor test Battery monitor autoEconomy Operation Economy OperationTechnical data System SpecificationsSystem Specifications InputHow to Contact APC How to Contact APC