APC DP300E Series manual Stop Start and Operating the External Service Bypass Panel, Stop stand-by

Page 5

Stop, Start & Operating the External Service Bypass Panel

WARNING!

Please read chapter 2.4.1 “Switching off” in this User Guide, if UPS has to be stopped for more than 48 hours.

2.0Stop – Start and Operating the External Service Bypass Panel

2.1General

CAUTION!

To avoid possible personal injury or equipment damage, be aware that there may be AC voltage at the UPS’s output terminals/receptacles any time AC input power or DC battery voltage is applied. The UPS can provide output voltage from the batteries even when there is no AC input line voltage. When AC voltage is present, the UPS can provide output voltage even when the batteries are disconnected. If you want to be certain that there is no UPS output voltage, always disconnect the AC input source, switch off the UPS, AND switch off the DC. TEST BEFORE TOUCHING!

Some units have been programmed at the factory for autostart. When this para- meter is programmed to be on, the unit will automatically switch on whenever utility (AC line) is applied. To switch this parameter off, see chapter 4.0.

For safety reasons, only qualified service personnel should do a complete start-up or shut-down of the UPS whenever this is necessary. The qualified service person should follow the instructions in the User and Installation Manual. The UPS must be completely shut down before service or before the UPS is taken out of operation for more than 24 hours.

Although users cannot completely start-up or shut down the unit, they can switch the UPS into standby mode and return it to normal operation by following the instructions below. (In stand-by mode, the UPS does not provide output voltage).

WARNING!

If the UPS system is installed with a service bypass panel, and the load equipment must remain energized from utility, refer to operating service bypass panel before proceeding chapter 2.2 - 2.5.

2.2Stop (stand-by)

Action

Display shows

Description

Open the front door

System off

Alarm LED lights. Acoustic

and activate the red

“OFF” push-button

 

alarm sounds for 30 seconds.

 

 

 

2.3Start (from stand-by)

Action

Display shows

Open the front door and

Normal operation

activate the green “ON”

Load power xx%

push-button

 

 

 

7OA0004 US rev. 02

User Guide Silcon DP300E Series 480V 400-500kVA

5

Image 5
Contents User Guide Silcon DP300E Series 480V 400-500kVA Silcon DP300E Series 480V 400-500kVA User GuideImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStart from stand-by Stop Start and Operating the External Service Bypass PanelStop stand-by Display shows Stop for complete power downSwitching off Silcon DP3400E DP3500E Starting up Silcon DP3400E DP3500E Start from complete power downBypassing the UPS Single Utility Dual UtilityAction Display shows Lamp indication on bypass panelSingle Utility Switching the system from external bypass into normalUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Keyboard description OperationOperation Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersKeys used for programming Programming example switch to bypass operation438 Programming of system configuration parameters346 326Programming example change charge voltage to Installation of new batteries Programming of battery monitorParallel programming/operation Description of settingsProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Other reasons for parallel operation alarm Parallel operation alarms GeneralAlarm texts conc. parallel operation Description MeasurementsReading Out Measurements Alarms What To Do AlarmsAlarm stack Alarm messagesDisplaying the events stack Mode CommentsEvents logger Possible alarm Description Action Possible alarmsTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanActions Display shows Battery capacity testFunctionality of battery test Battery monitor testBack-up time Monitor functionBattery monitor test Operation of the battery monitorBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC