APC DP300E Series Single Utility, Switching the system from external bypass into normal, Action

Page 9

Stop, Start & Operating the External Service Bypass Panel

Single Utility

2.6.2 Switching the system from external bypass into normal

 

UPS operation

Dual Utility

NOTE:

If battery has been discon- nected please refer to “Starting Up” in Chapter 2.5.1 to connect battery(-ies) again.

Action

1.Turn the input switch (Q001) to position “1”. If dual utility is present, turn the bypass input switch (Q010) to position “1”.

2.Wait 10 sec. Open the UPS front door and press the green “ON“ key

3.Press on the keyboard

4.Press or on the keyboard until

5. Press

on the keyboard

6.Press on the keyboard

7.Check lamp indication on the service bypass panel

8.Turn the output switch (Q002) to position “1“

9.Turn the bypass switch (Q003) to position “0“

10.Press on the keyboard

11.Press or on the keyboard until

12. Press

on the keyboard

13.Press on the keyboard

14.Press on the keyboard

15.Press on the keyboard

Display shows

**System OFF**

Normal operation

load power 0%

Bypass operation

: NO

Bypass operation

: YES

Lamp indication on bypass panel

The green lamp (H002) above the output switch handle (Q002) lights

Now the green lamp (H003) above the bypass switch handle (Q003) lights too

Only the green lamp (H003) above the bypass switch handle (Q003) lights

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation load power xx%

No lamps on the bypass panel light any longer

7OA0004 US rev. 02

User Guide Silcon DP300E Series 480V 400-500kVA

9

Image 9
Contents User Guide Silcon DP300E Series 480V 400-500kVA Silcon DP300E Series 480V 400-500kVA User GuideImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStop Start and Operating the External Service Bypass Panel Stop stand-byStart from stand-by Stop for complete power down Switching off Silcon DP3400E DP3500E Display shows Starting up Silcon DP3400E DP3500E Start from complete power downBypassing the UPS Single Utility Dual UtilityAction Display shows Lamp indication on bypass panelSingle Utility Switching the system from external bypass into normalUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersKeys used for programming Programming example switch to bypass operation438 Programming of system configuration parameters346 326Programming example change charge voltage to Installation of new batteries Programming of battery monitorParallel programming/operation Description of settingsProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Parallel operation alarms General Alarm texts conc. parallel operationOther reasons for parallel operation alarm Measurements Reading Out MeasurementsDescription Alarms What To Do AlarmsAlarm stack Alarm messagesMode Comments Events loggerDisplaying the events stack Possible alarm Description Action Possible alarmsTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanActions Display shows Battery capacity testFunctionality of battery test Battery monitor testBack-up time Monitor functionBattery monitor test Operation of the battery monitorBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC