APC DP300E Series manual Battery monitor test, Back-up time, Monitor function

Page 34

Preventive Maintenance

8.5 Battery monitor test

The battery monitor has two main purposes:

1.To show remaining back-up time, when the UPS operates in battery operation

2.To monitor the condition of the battery, during test or normal battery operation

8.5.1 Back-up time

The back-up time in the batteries is shown in the display, when UPS runs in battery operation. The back-up time is valid for the actual load on the UPS, however, if load changes, the actual back-up time will change too. The shown back-up time is also compensated for battery temperature changes, if a temperature sensor has been installed and calibrated.

8.5.2 Monitor function

During a test the battery monitor discharges 25% of the energy in the battery.

The monitor can detect, when a battery is weak, or if it is defective. The UPS gives an alarm, if one of the errors is detected. The criteria for the alarms are:

Battery weak alarm is given, when the measured battery capacity is less than 75% of the original capacity.

Battery detect alarm is given, when the measured battery capacity is less than 50% of the original capacity.

8.5.3 Functionality of battery test

The test can be started manually or automatically from the user stack.

The automatic test is enabled in the user stack and can be set to 3 or 6 months. When automatic test is enabled, the UPS performs a battery test every 3 or 6 months independent on manually activated battery tests. If conditions for starting a test are not correct at the moment where automatic test is going to start, the test will be skipped.

Conditions for starting a battery monitor test:

A battery monitor test can only be started if the battery is fully charged (capacity = 100%).

The UPS is operating in normal operation.

The test is interrupted if:

The error “battery defective” is encountered.

If utility fail during battery monitor test.

The red OFF button is pressed.

If “EPO” emergency power off is activated.

If external shutdown is accepted.

After the test the UPS returns to normal operation.

The battery monitor test can be performed with load in the range of 10-150%. If the load exceeds this level, faulty results may occur.

7OA0004 US rev. 02

34

User Guide Silcon DP300E Series 480V 400-500kVA

Image 34
Contents Silcon DP300E Series 480V 400-500kVA User Guide User Guide Silcon DP300E Series 480V 400-500kVAImportant Safety Instructions Table of Contents General IntroductionIntroduction Display unitStop stand-by Stop Start and Operating the External Service Bypass PanelStart from stand-by Switching off Silcon DP3400E DP3500E Stop for complete power downDisplay shows Start from complete power down Starting up Silcon DP3400E DP3500EAction Display shows Single Utility Dual UtilityBypassing the UPS Lamp indication on bypass panelUPS operation Switching the system from external bypass into normalSingle Utility ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programming346 Programming of system configuration parameters438 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesProgramming parameters for advanced parallel operation Description of settingsParallel programming/operation Programming guideProgramming example Highest Station No Alarm texts conc. parallel operation Parallel operation alarms GeneralOther reasons for parallel operation alarm Reading Out Measurements MeasurementsDescription Alarm stack AlarmsAlarms What To Do Alarm messagesEvents logger Mode CommentsDisplaying the events stack Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Battery Preventive MaintenancePreventive Maintenance FanBattery capacity test Actions Display showsBack-up time Battery monitor testFunctionality of battery test Monitor functionBattery monitor reset Operation of the battery monitorBattery monitor test Battery monitor autoEconomy Operation Economy OperationTechnical data System SpecificationsSystem Specifications InputHow to Contact APC How to Contact APC