8.4 Battery capacity test

NOTE:

Expect 16 hours recharge time after a battery capacity test before full backup time is available.

Actions

Display shows

1.Press

2.Press or

Battery capacity

until

test : xxx

3. Press

Battery capacity

test :

ON

 

Description

“xxx” is back-up time from last test – if no previous test has been performed or if the test has been aborted the display will show “???”!

A battery monitor test can be per- formed in the same way by selecting “Battery monitor test” in the display. However, this test will not start, unless the battery is fully charged.

The next step starts up the test! To abort press .

Starts the battery test.

(To interrupt a running test – perform

point 1-2 and then press key and

)

4.Press

5.Wait about 1 sec.

6.Wait until backup times expires and a short alarm sounds. (No alarm in battery monitor test if battery is OK)

Data stored

Battery operation time : xxx min.

Normal operation load power xx%

WARNING!

The UPS must at least be in operation for min. 16 hours in a 3 month period to ensure that the battery is sufficiently charged. If not the battery might be damaged.

Battery capacity

7. Press

test : xxx

Normal operation

8. Press

load power xx%

“xxx” is actual obtained back-up time in minutes. (Battery capacity test only).

Exits the parameter stack.

If not operated the system will auto- matically exit after 30 seconds.

If the UPS has to be taken out of operation for more than 48 hours, the battery must be disconnected in order to prevent it from being totally discharged. The information how to do this can be found in chapter 2.4.1.

7OA0004 US rev. 02

User Guide Silcon DP300E Series 480V 400-500kVA

33

Image 33
Contents User Guide Silcon DP300E Series 480V 400-500kVA Silcon DP300E Series 480V 400-500kVA User GuideImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStop Start and Operating the External Service Bypass Panel Stop stand-byStart from stand-by Stop for complete power down Switching off Silcon DP3400E DP3500EDisplay shows Starting up Silcon DP3400E DP3500E Start from complete power downBypassing the UPS Single Utility Dual UtilityAction Display shows Lamp indication on bypass panelSingle Utility Switching the system from external bypass into normalUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersKeys used for programming Programming example switch to bypass operation438 Programming of system configuration parameters346 326Programming example change charge voltage to Installation of new batteries Programming of battery monitorParallel programming/operation Description of settingsProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Parallel operation alarms General Alarm texts conc. parallel operationOther reasons for parallel operation alarm Measurements Reading Out MeasurementsDescription Alarms What To Do AlarmsAlarm stack Alarm messagesMode Comments Events loggerDisplaying the events stack Possible alarm Description Action Possible alarmsTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm Description Remote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanActions Display shows Battery capacity testFunctionality of battery test Battery monitor testBack-up time Monitor functionBattery monitor test Operation of the battery monitorBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC