APC 10-40KW 400V UPS manual Mm2 Output Cable, Fuses

Page 16

External Connection

NOTICE!

Check correct phase rotation of mains input voltage!!

Max. input/output cables: 120mm2. Battery: 70 mm2.

If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.

UPS

External

External

External PE

Maximum

External

 

Input

Input Cable

Cable

External

Output

 

Fuses* FM

[mm2]

[mm2]

Output

Cable

 

[A]

380-415V

 

Fuses*

[mm2]

 

380-415V

 

 

[A]

 

 

 

 

 

 

 

40kW

80

25

16

63

16

 

 

 

 

 

 

*DIN gL types

NOTICE!

All cable dimensions are recommended sizes only. Refer to local legal regulations.

UPS

External Alarm

External System

External Battery

External

 

Cable max.

Earth Cable

Breaker

Battery Cable

 

[mm2]

[mm2]**

[A]

[mm2]

 

 

 

 

 

40KW

2

10

63

16

 

 

 

 

 

PVC cables isolated to withstand ambient temperature of max. 30oC.

** Must be rated as external PE cable if mains system is not supplying PE.

NOTICE!

Install gland plate in bottom of unit.

990-4050

16

Installation Guide APC Silcon 10-40kW 400V UPS

Image 16
Contents 10-40kW 400V UPS Installation Guide Safety Symbols used in this manual Installation Guide APC Silcon 10-40kW 400V UPSThank You Contents System Specifications Warranty10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site 1xBP 2xBP 3xBPCabinets Footprint 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer3 1000mm Cabinet for 10-20kW UPS with 3xBP 4 600mm Cabinet for 40kW UPS without Batteries5 1000mm Cabinet for 40kW UPS with 2xBP Connecting the UPS Connecting the 10-20kW UPSExternal Connection External ConnectionOutput Battery CableFuses 10kW 20kW Connecting the 40kW UPS InputMm2 Output Cable FusesMm2 40KWSystem Integration Interface Connections Parallel Board Terminal Blocks X003/X004 Anxiliary ContactsX005 Output Relays Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis X50 and a serial portSafety Warnings APC Silcon Triple ChassisProduct Description 2.1Monitoring Port2.4Optional Power Input Installing Management Peripherals2.3LEDs If the LED is… Then the Silcon Triple Chassis…3.2Installing Management Peripheral Cards 3.1Order of Management Peripheral CardsManagement Priority Position Peripheral Card 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Problem Possible Cause Solution Troubleshooting5.1If Problems Persist External Connection External Connection Physical 6.2Power, Physical, and Environmental SpecificationsEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets Diagram UPS with Battery Cabinet 5.1Installation of BatteriesSilcon Battery Breaker Box/Fuse-box Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable ShortCircuit Current kA 10 kW 20 kWBattery Breaker Box Connection Diagram BatteryFuse-box Fuse-box Connection Diagram External Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Action Lamp indication On Service Bypass PanelDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Extension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async 1.1Connections Without Converter Host DTE Remote Display DTE1.2Connections With Converter Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.2Communication Fault Remote Display Setting3.6Alarms Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerConnecting Isolation Transformer Cable SignalIsolation External External PE Input Fuses Input Cable Cable mm2 Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Back-up Time / Dimensions / WeighWarranty WarrantyAPC Silcon Series Limited Factory Warranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark