APC 10-40KW 400V UPS manual Battery Breaker Box Connection Diagram

Page 42

External Connection

4.8.2 Battery Breaker Box Connection Diagram

Battery 1

Battery 2

UPS Battery 1

UPS Battery 2

Main cables are connected directly to component terminals

X009 LED signal from UPS “OK to operate corresponding MCCB”

X010 MCCB position signals for UPS

X011 Trip for emergency stop (220-240V AC)

990-4050

42

Installation Guide APC Silcon 10-40kW 400V UPS

Image 42
Contents 10-40kW 400V UPS Installation Guide Installation Guide APC Silcon 10-40kW 400V UPS Safety Symbols used in this manualThank You Contents 10.0 How to Contact APC System SpecificationsWarranty AppendixTools and Equipment IntroductionIntroduction ToolsUnpacking UnpackingPlease Recycle Requirements on Site InstallationInstallation 1xBP 2xBP 3xBPCabinets Footprint 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer3 1000mm Cabinet for 10-20kW UPS with 3xBP 4 600mm Cabinet for 40kW UPS without Batteries5 1000mm Cabinet for 40kW UPS with 2xBP External Connection Connecting the UPSConnecting the 10-20kW UPS External ConnectionBattery Cable OutputFuses 10kW 20kW Connecting the 40kW UPS InputMm2 Mm2 Output CableFuses 40KWSystem Integration Interface Connections X005 Output Relays Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis X50 and a serial portProduct Description Safety WarningsAPC Silcon Triple Chassis 2.1Monitoring Port2.3LEDs 2.4Optional Power InputInstalling Management Peripherals If the LED is… Then the Silcon Triple Chassis…Management Priority Position Peripheral Card 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause Solution5.1If Problems Persist External Connection External Connection 6.2Power, Physical, and Environmental Specifications PhysicalEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets 5.1Installation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box Circuit Current kA 10 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short 20 kWBattery Breaker Box Connection Diagram BatteryFuse-box Fuse-box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async 1.2Connections With Converter 1.1Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.6Alarms 3.2Communication FaultRemote Display Setting Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerIsolation External External PE Connecting Isolation TransformerCable Signal Input Fuses Input Cable Cable mm2 Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Technical Data System SpecificationsSystem Specifications Back-up Time / Dimensions / WeighWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Corporate How to Contact APCHow to Contact APC APC Denmark