APC 10-40KW 400V UPS manual External Connection

Page 35

External Connection

800mm Battery Cabinet

1000mm Battery Cabine

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.7.3 Mounting Batteries

WARNING!

Open front door of UPS and unscrew front cover.

Do not install battery drawers in UPS frame until all AC/DC sources are disconnected. Disconnect charging source prior to connecting batteries. Ensure that battery breakers F001 and F002 are set to position “off”.

WARNING!

Before proceding, ensure that power supplies have been disconnected from UPS for a minimum of 5 minutes.

Unscrew front frame of UPS and slide frame down as shown above.

Battery drawers may be installed after removal of front cover.

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

35

Image 35
Contents 10-40kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 10-40kW 400V UPSSafety Symbols used in this manual Contents Appendix System SpecificationsWarranty 10.0 How to Contact APCTools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingPlease Recycle 1xBP 2xBP 3xBP InstallationInstallation Requirements on SiteCabinets 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer Footprint4 600mm Cabinet for 40kW UPS without Batteries 3 1000mm Cabinet for 10-20kW UPS with 3xBP5 1000mm Cabinet for 40kW UPS with 2xBP External Connection Connecting the UPSConnecting the 10-20kW UPS External ConnectionFuses 10kW 20kW Battery CableOutput Input Connecting the 40kW UPS40KW Mm2 Output CableFuses Mm2System Integration Interface Connections Parallel Board Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysExternal Connection External Control Cables Power CablesCommunication Interface Board X50 and a serial port Connecting of APC Silcon Tripel Chassis2.1Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… 2.4Optional Power InputInstalling Management Peripherals 2.3LEDs3.3Daisy-chaining the APC Silcon Triple Chassis 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards Management Priority Position Peripheral CardManagement Peripheral Draw mA 5.1If Problems Persist TroubleshootingProblem Possible Cause Solution External Connection External Connection Environmental 6.2Power, Physical, and Environmental SpecificationsPhysical Important Safety Instructions APC Silcon Battery CabinetsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets Silcon 5.1Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box 20 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short Circuit Current kA 10 kWBattery Battery Breaker Box Connection DiagramFuse-box Fuse-box Connection Diagram External Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Pin Connections for cable from host to ME800A-R2 Host 1.1Connections Without ConverterHost DTE Remote Display DTE 1.2Connections With ConverterRemote Display Cables 2.2Remote Display Power SupplyRemote Display Use 3.2Communication FaultRemote Display Setting 3.6AlarmsIsolation Transformer Height mm Width mm Depth mm Weight kgInput Fuses Input Cable Cable mm2 Output Temp FM a Connecting Isolation TransformerCable Signal Isolation External External PEOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Back-up Time / Dimensions / Weigh System SpecificationsSystem Specifications Technical DataAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate