APC 10-40KW 400V UPS manual 1.1Connections Without Converter, Host DTE Remote Display DTE

Page 75

Options/Accessories

6.6.1.1Connections Without Converter

Connect a 25-pin female Sub-D and a 9-pin male Sub-D connector with a 3-wire shielded cable, as shown in the table below. Connect shield at one end only.

Pin Connection for Interconnection Cable (without converter):

Host (DTE)

Remote Display (DTE)

 

 

25-pin female

9-pin male

pin No.

pin No.

 

 

 

 

2

(TXD)

2

(RXD)

 

 

 

 

3

(RXD)

3

(TXD)

 

 

 

 

7

(GND)

5

(GND)

 

 

House (shield)

No Connection

 

 

 

 

6.6.1.2Connections With Converter

Connections to be made according to converter manual.

Pinconnection example only:

Pin Connections for cable from host to ME800A-R2.

Host

ME800A-R2

(DTE)

(DCE)

 

 

25-pin female

25-pin male

pin No.

pin No.

 

 

 

2

(TXD)

3

 

 

 

3

(RXD)

2

 

 

 

7

(GND)

7

 

 

House (Shield)

No connection

 

 

 

Pin connection for cable from

ME800A-R2 to Remote Display

ME800A-R2

Remote Display

(DCE)

(DTE)

 

 

25-pin male

9-pin male

pin No.

pin No.

 

 

 

3

2

(RXD)

 

 

 

2

3

(TXD)

 

 

 

7

5

(GND)

 

 

No connection

House (Shield)

 

 

 

The ME800A-R2 must be set up as a DCE with no RTS/DTR control.

The interconnection cable between the two ME800A-R2 boxes is a 4-wire twisted pair telephone cable with or without shield. The shield improves noise immunity but reduces maximum communication distance.

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

75

Image 75
Contents 10-40kW 400V UPS Installation Guide Installation Guide APC Silcon 10-40kW 400V UPS Safety Symbols used in this manualThank You Contents Appendix System SpecificationsWarranty 10.0 How to Contact APCTools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingPlease Recycle 1xBP 2xBP 3xBP InstallationInstallation Requirements on SiteCabinets 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer Footprint4 600mm Cabinet for 40kW UPS without Batteries 3 1000mm Cabinet for 10-20kW UPS with 3xBP5 1000mm Cabinet for 40kW UPS with 2xBP External Connection Connecting the UPSConnecting the 10-20kW UPS External ConnectionBattery Cable OutputFuses 10kW 20kW Input Connecting the 40kW UPS40KW Mm2 Output CableFuses Mm2System Integration Interface Connections Parallel Board Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysExternal Connection External Control Cables Power CablesCommunication Interface Board X50 and a serial port Connecting of APC Silcon Tripel Chassis2.1Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… 2.4Optional Power InputInstalling Management Peripherals 2.3LEDs3.3Daisy-chaining the APC Silcon Triple Chassis 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards Management Priority Position Peripheral CardManagement Peripheral Draw mA Troubleshooting Problem Possible Cause Solution5.1If Problems Persist External Connection External Connection 6.2Power, Physical, and Environmental Specifications PhysicalEnvironmental Important Safety Instructions APC Silcon Battery CabinetsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets 5.1Installation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box 20 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short Circuit Current kA 10 kWBattery Battery Breaker Box Connection DiagramFuse-box Fuse-box Connection Diagram External Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Pin Connections for cable from host to ME800A-R2 Host 1.1Connections Without ConverterHost DTE Remote Display DTE 1.2Connections With ConverterRemote Display Cables 2.2Remote Display Power SupplyRemote Display Use 3.2Communication FaultRemote Display Setting 3.6AlarmsIsolation Transformer Height mm Width mm Depth mm Weight kgInput Fuses Input Cable Cable mm2 Output Temp FM a Connecting Isolation TransformerCable Signal Isolation External External PEOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Back-up Time / Dimensions / Weigh System SpecificationsSystem Specifications Technical DataWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate