APC 10-40KW 400V UPS manual Installation Guide APC Silcon 10-40kW 400V UPS, Thank You

Page 2

Thank You!

Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation.

The installation and use of this product must comply with national, federal, state, municipal and local codes.

Safety Symbols used in this manual

WARNING! Indicates a hazard which, if not avoided, could result in injury or death.

CAUTION! Indicates a hazard which, if not avoided, could result in damage to the product or other property.

NOTICE! Read and pay attention to this important information.

WARNING!

This UPS unit contains hazardous AC and DC voltages. Only qualified electricians should install the UPS, AC line and external batteries, and must be familiar with batteries and battery installation.

Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources of AC and DC power.

As the UPS has no built-in disconnection devices to switch off external AC and DC input power, ensure that disconnection devices are provided as separate parts in connection with the installation!

The installer must provide each external disconnecting device for this UPS system with labels with the following text:

“Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide before working on circuit”

AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated from either batteries or mains. To avoid equipment damage or personal injury, always assume that there may be voltage at UPS output.

This system is equipped with an auto-start function. If activated, the system may start without warning. Refer to the “Programming” section of this guide for information on de-activation.

TEST BEFORE YOU TOUCH!

To reduce the risk of fire or electric shocks, install the UPS and external batteries in a temperature and humidity controlled indoor area, free of conductive contaminants.

UPS batteries are high-current sources. Shorting battery terminals or DC terminals, DC busbars can cause severe arcing, equipment damage and injury. A short circuit can cause a battery to explode. Always wear protective clothing and eye protection and use insulated tools when working on batteries.

CAUTION!

This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the ESD procedures, you may cause severe damage to electronic components.

990-4050

2

Installation Guide APC Silcon 10-40kW 400V UPS

Image 2
Contents 10-40kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 10-40kW 400V UPSSafety Symbols used in this manual Contents 10.0 How to Contact APC System SpecificationsWarranty AppendixTools and Equipment IntroductionIntroduction ToolsUnpacking UnpackingPlease Recycle Requirements on Site InstallationInstallation 1xBP 2xBP 3xBPCabinets Footprint 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer3 1000mm Cabinet for 10-20kW UPS with 3xBP 4 600mm Cabinet for 40kW UPS without Batteries5 1000mm Cabinet for 40kW UPS with 2xBP External Connection Connecting the UPSConnecting the 10-20kW UPS External ConnectionFuses 10kW 20kW Battery CableOutput Connecting the 40kW UPS InputMm2 Mm2 Output CableFuses 40KWSystem Integration Interface Connections X005 Output Relays Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis X50 and a serial portProduct Description Safety WarningsAPC Silcon Triple Chassis 2.1Monitoring Port2.3LEDs 2.4Optional Power InputInstalling Management Peripherals If the LED is… Then the Silcon Triple Chassis…Management Priority Position Peripheral Card 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA 5.1If Problems Persist TroubleshootingProblem Possible Cause Solution External Connection External Connection Environmental 6.2Power, Physical, and Environmental SpecificationsPhysical APC Silcon Battery Cabinets Important Safety InstructionsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets Silcon 5.1Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Circuit Current kA 10 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short 20 kWBattery Breaker Box Connection Diagram BatteryFuse-box Fuse-box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance 1.2Connections With Converter 1.1Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.6Alarms 3.2Communication FaultRemote Display Setting Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerIsolation External External PE Connecting Isolation TransformerCable Signal Input Fuses Input Cable Cable mm2 Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Technical Data System SpecificationsSystem Specifications Back-up Time / Dimensions / WeighAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix APC Corporate How to Contact APCHow to Contact APC APC Denmark