APC 10-40KW 400V UPS manual Appendix

Page 89

Appendix

Notes:

1.Nominal input current based on rated load.

2.Maximum input current based on rated load + full battery recharge. Full battery recharge assumed to increase input current with 10%.

3.Nominal power consumption (column 1c) based on nominal input current (1e) and the corresponding input voltage (1a).

4.Maximum power consumption (1d) based on maximum input current (1f) and the corresponding input voltage (1a).

5.Suggested input overcurrent protection (1h) based on continous full load maximum input current (1f). MCCB breaker selection based on continous full load nominal input current (1e) is acceptable, provided battery recharge time is short.

6.Fuses according to DIN LV HRC type gL, 500V assumed. MCCB load capacity must be 8xIn (nominal current) for minimum 10ms.

7.Suggested load side overcurrent protection (3b) based on nominal output current (3a).

8.Nominal battery voltage assumed to be 2V/cell (Lead technologi).

9.Recommended cable sizes, see "External Connection" section of this guide. CAUTION! Cable sizes must comply with national and/or local legal regulations.

10.Nominal battery discharge current (2c) based on full rated load and nominal battery voltage (2V/cell).

11.Maximum battery discharge current (2d) based on full rated load and battery voltage at end of discharge (1.7V/cell).

12.Full load discharge power from battery based on nominal battery discharge current

(2c) x nominal battery voltage (2x192cells x 2V/cell), or maximum battery discharge current (2d) x battery voltage at end of discharge (2x192cells x 1.7 V/cell).

13.Heat dissipation based on nominal full load capacity and linear load.

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

89

Image 89
Contents 10-40kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 10-40kW 400V UPSSafety Symbols used in this manual Contents Warranty System Specifications10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site 1xBP 2xBP 3xBPCabinets 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer Footprint4 600mm Cabinet for 40kW UPS without Batteries 3 1000mm Cabinet for 10-20kW UPS with 3xBP5 1000mm Cabinet for 40kW UPS with 2xBP Connecting the 10-20kW UPS Connecting the UPSExternal Connection External ConnectionFuses 10kW 20kW Battery CableOutput Input Connecting the 40kW UPSFuses Mm2 Output CableMm2 40KWSystem Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts Parallel BoardX005 Output Relays Parallel BoardExternal Connection External Control Cables Power CablesCommunication Interface Board X50 and a serial port Connecting of APC Silcon Tripel ChassisAPC Silcon Triple Chassis Safety WarningsProduct Description 2.1Monitoring PortInstalling Management Peripherals 2.4Optional Power Input2.3LEDs If the LED is… Then the Silcon Triple Chassis…3.1Order of Management Peripheral Cards 3.2Installing Management Peripheral CardsManagement Priority Position Peripheral Card 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA 5.1If Problems Persist TroubleshootingProblem Possible Cause Solution External Connection External Connection Environmental 6.2Power, Physical, and Environmental SpecificationsPhysical Important Safety Instructions APC Silcon Battery CabinetsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets Silcon 5.1Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Ampere Connection Max Dimensions Weight Rating Cable Short Battery Breaker BoxCircuit Current kA 10 kW 20 kWBattery Battery Breaker Box Connection DiagramFuse-box Fuse-box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Host DTE Remote Display DTE 1.1Connections Without Converter1.2Connections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Cables 2.2Remote Display Power SupplyRemote Display Setting 3.2Communication Fault3.6Alarms Remote Display UseIsolation Transformer Height mm Width mm Depth mm Weight kgCable Signal Connecting Isolation TransformerIsolation External External PE Input Fuses Input Cable Cable mm2 Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Back-up Time / Dimensions / WeighAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark