APC 10-40KW 400V UPS manual Extension of Remote Display Communication Distance

Page 74

Options/Accessories

6.6Remote Display

With the remote display unit data may be displayed at distances of up to 25 m from UPS. For extended communication distance, see section below.

Remote display may easily be connected to UPS via one of the two serial communication ports on the communication interface board.

To obtain a transmission distance of up to 3.2 km normal RS232C signal levels must be converted to a long distance communication standard. The converter must be placed outside the UPS cabinet.

6.6.1 Extension of Remote Display Communication Distance

Remote display communicates with the UPS through a 3-wire RS232 interface. Remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector. Communication speed: 9600 bps.

For communication distances, see Table 1. Insert converters if longer distances are necessary, or if communication cables are led through magnetically noisy areas. Converters must comply with local regulations

Table 1: Remote Display Communication Extensions

 

Standard

Short-haul

 

(RS232)

Modem Async

 

 

 

Max. distance

80/25 ft/m

10000/3200 ft/m

 

 

 

Converter Manufacture

No converter

BLACK BOX

Art. Code

 

ME800A-R2

 

 

 

RS232 BLACK BOX connector

 

Sub-D 25-pin female

 

 

 

BLACK BOX interconnector

 

4-screw terminal

 

 

 

Two converter boxes are required for a communication distance extension: One

box near the UPS for the conversion from RS232C to a long distance communication standard, and another box at the other end to convert back to RS232C, which is to be connected to the Remote Display. The converter provides optical signal insulation. Both converter boxes must be supplied by an uninterruptible power source.

990-4050

74

Installation Guide APC Silcon 10-40kW 400V UPS

Image 74
Contents 10-40kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 10-40kW 400V UPSSafety Symbols used in this manual Contents 10.0 How to Contact APC System SpecificationsWarranty AppendixTools and Equipment IntroductionIntroduction ToolsUnpacking UnpackingPlease Recycle Requirements on Site InstallationInstallation 1xBP 2xBP 3xBPCabinets Footprint 1 600mm UPS Cabinet with 1xBP I or Isolation Transformer3 1000mm Cabinet for 10-20kW UPS with 3xBP 4 600mm Cabinet for 40kW UPS without Batteries5 1000mm Cabinet for 40kW UPS with 2xBP External Connection Connecting the UPSConnecting the 10-20kW UPS External ConnectionFuses 10kW 20kW Battery CableOutput Connecting the 40kW UPS InputMm2 Mm2 Output CableFuses 40KWSystem Integration Interface Connections X005 Output Relays Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis X50 and a serial portProduct Description Safety WarningsAPC Silcon Triple Chassis 2.1Monitoring Port2.3LEDs 2.4Optional Power InputInstalling Management Peripherals If the LED is… Then the Silcon Triple Chassis…Management Priority Position Peripheral Card 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA 5.1If Problems Persist TroubleshootingProblem Possible Cause Solution External Connection External Connection Environmental 6.2Power, Physical, and Environmental SpecificationsPhysical APC Silcon Battery Cabinets Important Safety InstructionsPreparing Batteries External Connection External Connection External Connection Final Checks APC Silcon Battery Cabinets Silcon 5.1Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Circuit Current kA 10 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short 20 kWBattery Breaker Box Connection Diagram BatteryFuse-box Fuse-box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance 1.2Connections With Converter 1.1Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.6Alarms 3.2Communication FaultRemote Display Setting Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerIsolation External External PE Connecting Isolation TransformerCable Signal Input Fuses Input Cable Cable mm2 Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Technical Data System SpecificationsSystem Specifications Back-up Time / Dimensions / WeighAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix APC Corporate How to Contact APCHow to Contact APC APC Denmark