Toshiba S20LP instruction manual Station down information, Possible error message are as follows

Page 42

6 F 3 B 0 3 5 6

(3)Station down information

If the S-LS connecting station is in Down mode, the error message can be monitored as follows.

R:RAS Information

4:Station Down Information

Possible error message are as follows.

Error code

Error message

meanings

 

 

 

10H

Watch dog timer error

Watch dog timer error occured

 

 

 

20H

Overrun

Reception transaction is overrun

 

 

 

40H

Jabber timeout

Abnormal long frame (500ms or more) was

 

 

transmitted

 

 

 

60H

Hardware error

CPU, RAM, ROM or peripheral LSI is abnormal

 

 

Station number illegal

 

 

 

6FH

Undefined instruction

CPU could not execute the instruction

 

executing

 

 

 

 

77H

Receive buffer overflow

Receive buffer overflow occurred

 

 

 

If these errors cannot be reset by power off/on again (except Station number illegal), replace the station.

41

Image 42
Contents T2N/T3H stations Important Information Preface Contents System configuration Introduction to S20LPStation hardware ∙ OverviewT2N include of S20LP Port SN325 SN325∙ Status LEDs S20LP port for T2N PU245NFor SN325 ∙ Reset switch only SN325 ∙ Station number setting switches∙ Transmission cable connectors ∙ Loader portLS overview Menu⎯ 10 ⎯ Specifications S20LP system specificationsS20LP-station specifications Scan transmission overview Setting the data send block by S-LS Allocation and network assignment by T-PDSSetting for data linkage Station number settingSettings on T-PDS Link PDS screen example Block Send Receive ⎯ 18 ⎯ Global ⎯ 20 ⎯ Settings on S-LS ⎯ 22 ⎯ ⎯ 23 ⎯ ⎯ 24 ⎯ ∙ Scan Transmission ∙ Scan Access∙ Start with Standby mode ∙ Message Transmission∙ Target Scan Time Data linkage example ∙ Settings on T-PDS Setting on S-LS LS setting screen 2 for STN #2 Cable connections ∙ Station down RAS functionBehavior in trouble ∙ Transmission cable breakageSelf-diagnostic function At initialization at power onDuring operation LED indication SN325T2N RAS information monitored in T2N/T3H Station status Online mapStandby map Loop map Only T2NRAS information monitored on S-LS Number 1-64 on the screen shows the Station numberSelf Station Station No.01 Offline Select the Station Number Click the Status Display Possible error message are as follows Station down informationInstruction format Instruction SpecificationExpanded data transfer instruction FunctionParameter and construction Transfer parameter tableSample program ∙ OperationRemarks Computer link protocol Message transmissionMessage transmission PC link protocol∙ Send Transfer parameters a CMDStatus B TermSTS Status Meaning Detailed Information Send completion status PC link protocol transmission Data write Transfer parametersRID Status See 7.3 5 for details on bits C, D, E, and F Important itemsXW/YW PC link protocol transmission Data read ⎯ 57 ⎯ SW067 Write enabled PC link protocol transmission program RemarksLength END Appendix Scan cycle⎯ 63 ⎯ PDS remote programming PDS Setup options screen