Toshiba S20LP instruction manual ∙ Target Scan Time

Page 27

6 F 3 B 0 3 5 6

Target Scan Time

A time factor for limiting the time assigned for the Message transmission. The actual Scan time (time of Token passes all stations) is either longer one the Target Scan time or time for Scan transmission. (see Apendix A.1)

The Target Scan time should be the same value in all stations connected to the S20LP network (layer). The Target Scan time can be selected from the combo box, select the target cycle time you want to set. Click on the "OK" or "Renew" button. The data you set is transmitted to the corresponding station.

3.07 8.19 13.3 24.6 45.1

4.10 9.22 14.3 28.7 49.2

5.12 10.2 15.4 32.8 53.2

6.14 11.3 16.3 36.9 57.3

7.17 12.3 20.5 41.0 61.4

(Note 1) If Message transmission cannot work normally or a S20LP-station becomes Error down by Receive buffer overflow, the time for Message transmission is not enough. In such case, increase the Target Scan time value.

When the settings are correctly written into the S20LP-station's EEPROM, it is displayed on the screen as below.

(6)Change connection to other stations, and repeat (2) to (5).

S-LS remote setting (without changing connection) is also available by selecting the station number. In this case, change the station mode to "STANDBY" by S-LS before setting. After all setting complete, change the station mode to “ONLINE” by S-LS.

26

Image 27
Contents T2N/T3H stations Important Information Preface Contents Introduction to S20LP System configurationStation hardware ∙ OverviewT2N include of S20LP Port SN325 SN325∙ Status LEDs S20LP port for T2N PU245NFor SN325 ∙ Loader port ∙ Station number setting switches∙ Transmission cable connectors ∙ Reset switch only SN325Menu LS overview⎯ 10 ⎯ Specifications S20LP system specificationsS20LP-station specifications Scan transmission overview Allocation and network assignment by T-PDS Setting the data send block by S-LSSetting for data linkage Station number settingSettings on T-PDS Link PDS screen example Block Send Receive ⎯ 18 ⎯ Global ⎯ 20 ⎯ Settings on S-LS ⎯ 22 ⎯ ⎯ 23 ⎯ ⎯ 24 ⎯ ∙ Message Transmission ∙ Scan Access∙ Start with Standby mode ∙ Scan Transmission∙ Target Scan Time Data linkage example ∙ Settings on T-PDS Setting on S-LS LS setting screen 2 for STN #2 Cable connections ∙ Transmission cable breakage RAS functionBehavior in trouble ∙ Station downSelf-diagnostic function At initialization at power onDuring operation LED indication SN325T2N RAS information monitored in T2N/T3H Online map Station statusLoop map Only T2N Standby mapNumber 1-64 on the screen shows the Station number RAS information monitored on S-LSSelf Station Station No.01 Offline Select the Station Number Click the Status Display Station down information Possible error message are as followsFunction Instruction SpecificationExpanded data transfer instruction Instruction formatTransfer parameter table Parameter and construction∙ Operation Sample programRemarks PC link protocol Message transmissionMessage transmission Computer link protocol∙ Send CMD Transfer parameters aStatus B TermSTS Status Meaning Detailed Information Send completion status Transfer parameters PC link protocol transmission Data writeRID Important items Status See 7.3 5 for details on bits C, D, E, and FXW/YW PC link protocol transmission Data read ⎯ 57 ⎯ SW067 Write enabled Remarks PC link protocol transmission programLength END Scan cycle Appendix⎯ 63 ⎯ PDS remote programming PDS Setup options screen