Toshiba S20LP Setting the data send block by S-LS, Allocation and network assignment by T-PDS

Page 14

6 F 3 B 0 3 5 6

Main terminal station, back-up terminal station and general station

When power is applied to each S20LP-station, one station must have station address number 1. The station of station number 1 becomes the main terminal station. The station of station number 2 becomes back-up terminal station. Normally stations, except station number 1, become the general stations. The main terminal station controls total timing of the S20LP network. If main terminal station is down, back-up terminal station (station number 2) becomes main terminal station on condition that the back-up enable flag is ON. If the back-up enable flag is OFF, back-up terminal is general station. If both the station of station number 1 and 2 is down, all stations become general station.

To be effective back-up terminal station, the address (1F44H) on the S20LP dual port memory must be set ON. To set the S20LP dual port memory, use the write instruction. Detailed information of write instruction see “T-series Instruction Set (Ladder, SFC)” (UM-TS03***- E004).

Setting the "data send block" (by S-LS)

On each station, the "data send block" is prespecified by using the S-LS. This setting is made by entering the starting addess and the size (number of send words). On a station, up to two "data send blocks" can be specified. (see Section 3.3)

I/O allocation and network assignment (by T-PDS)

On each T2N/T3H, the I/O allocation for S20LP-station and the network assignment are necessary. By using the T-PDS's I/O allocation function, allocate the S20LP-station as "TL-S" (T3H) or E/S (T2N). And by using the T-PDS's Network assignment function, assign (set "LINK" or "GLOBAL") the Link registers (W) to the S20LP-station's common memory (from 0 to 2048), Block by Block. (see Section 3.2)

Block 1: W0000 to W0063

Block 17: W1024 to W1087

Block 2: W0064 to W0127

Block 18: W1088 to W1151

Block 3: W0128 to W0191

Block 19: W1152 to W1215

Block 4: W0192 to W0255

Block 20: W1216 to W1279

Block 5: W0256 to W0319

Block 21: W1280 to W1343

Block 6: W0320 to W0383

Block 22: W1344 to W1407

Block 7: W0384 to W0447

Block 23: W1408 to W1471

Block 8: W0448 to W0511

Block 24: W1472 to W1535

Block 9: W0512 to W0575

Block 25: W1536 to W1599

Block 10: W0576 to W0639

Block 26: W1600 to W1663

Block 11: W0640 to W0703

Block 27: W1664 to W1727

Block 12: W0704 to W0767

Block 28: W1728 to W1791

Block 13: W0768 to W0831

Block 29: W1792 to W1855

Block 14: W0832 to W0895

Block 30: W1856 to W1919

Block 15: W0896 to W0959

Block 31: W1920 to W1983

Block 16: W0960 to W1023

Block 32: W1984 to W2047

T2N/T3H accesses the common memory only for the assigned Blocks. (This "Block" and S20LP's "Data send block" are different.)

"LINK" is normal assignment setting. "GLOBAL" is the setting for multi layers Scan transmission. (effective only in T3H)

13

Image 14
Contents T2N/T3H stations Important Information Preface Contents System configuration Introduction to S20LPT2N include of S20LP Port Station hardware∙ Overview SN325 SN325For SN325 ∙ Status LEDsS20LP port for T2N PU245N ∙ Reset switch only SN325 ∙ Station number setting switches∙ Transmission cable connectors ∙ Loader portLS overview Menu⎯ 10 ⎯ S20LP-station specifications SpecificationsS20LP system specifications Scan transmission overview Setting the data send block by S-LS Allocation and network assignment by T-PDSSettings on T-PDS Setting for data linkageStation number setting Link PDS screen example Block Send Receive ⎯ 18 ⎯ Global ⎯ 20 ⎯ Settings on S-LS ⎯ 22 ⎯ ⎯ 23 ⎯ ⎯ 24 ⎯ ∙ Scan Transmission ∙ Scan Access∙ Start with Standby mode ∙ Message Transmission∙ Target Scan Time Data linkage example ∙ Settings on T-PDS Setting on S-LS LS setting screen 2 for STN #2 Cable connections ∙ Station down RAS functionBehavior in trouble ∙ Transmission cable breakageDuring operation Self-diagnostic functionAt initialization at power on T2N LED indicationSN325 RAS information monitored in T2N/T3H Station status Online mapStandby map Loop map Only T2NRAS information monitored on S-LS Number 1-64 on the screen shows the Station numberSelf Station Station No.01 Offline Select the Station Number Click the Status Display Possible error message are as follows Station down informationInstruction format Instruction SpecificationExpanded data transfer instruction FunctionParameter and construction Transfer parameter tableSample program ∙ OperationRemarks Computer link protocol Message transmissionMessage transmission PC link protocol∙ Send Transfer parameters a CMDStatus B TermSTS Status Meaning Detailed Information Send completion status PC link protocol transmission Data write Transfer parametersRID Status See 7.3 5 for details on bits C, D, E, and F Important itemsXW/YW PC link protocol transmission Data read ⎯ 57 ⎯ SW067 Write enabled PC link protocol transmission program RemarksLength END Appendix Scan cycle⎯ 63 ⎯ PDS remote programming PDS Setup options screen