Toshiba S20LP instruction manual Parameter and construction, Transfer parameter table

Page 44

6 F 3 B 0 3 5 6

(4)Parameter and construction

 

Source parameter

 

Transfer size and status

 

 

 

 

 

A

Bank/CH

Type

B

Transfer size

 

 

 

 

 

A+1

Leading address

 

 

 

 

 

 

 

 

Destination parameter

 

 

 

C

Bank/CH

Type

 

 

 

C+1

Leading address

 

 

 

Transfer parameter table

Transfer object

 

 

Type

Leading address

Bank/CH

Transfer size

Status flag

 

 

 

 

 

 

 

 

 

 

 

T2N

 

0 to 127

 

1 to 128

 

XW/YW register

 

 

 

00H

 

0

 

None

 

T3H

0 to 511

1 to 256

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W register

 

 

01H

0 to 2047

0

1 to 256

None

 

 

 

 

 

 

 

 

LW register

 

 

02H

0 to 255

0

1 to 256

None

 

 

 

 

 

 

 

 

 

 

 

T2N

 

0 to 255

 

 

 

RW register

 

 

 

03H

 

0

1 to 256

None

 

T3H

0 to 999

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D register

 

 

04H

0 to 8191

0

1 to 256

None

 

 

 

 

 

 

 

 

 

 

 

T2N

 

0 to 1023

 

 

 

F register

 

 

 

03H

 

0

1 to 256

None

 

T3H

0 to 32767

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Expanded F register

 

T

05H

0 to 8191

1 to 15

1 to 256

None

(IC memory card)

 

3

 

 

 

 

 

 

 

0 to 65535

1

 

 

 

H

 

 

 

 

 

 

06H

 

 

1 to 256

None

 

 

 

 

0 to 57343

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Expanded F register

 

T

05H

0 to 8191

1 to 3

1 to 256

None

(T2N internal memory)

2

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

TOSLINE-S20LP

 

T2N

 

 

1

 

 

scan memory

 

 

 

10H

0 to 4095

 

1 to 256

None

 

T3H

1 or 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM

 

T2N

 

0 to 2047

 

1 to 256

 

 

 

 

 

20H

 

0

(Note 1)

None

 

 

T3H

0 to 8191

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note 1) When the communication is transfer source (receiving), the transfer size is 1 to 256. When it is destination (transmitting), the transfer size is 1 to 128 for T3H, 1 to 32 for T2N.

43

Image 44
Contents T2N/T3H stations Important Information Preface Contents System configuration Introduction to S20LPT2N include of S20LP Port Station hardware∙ Overview SN325 SN325For SN325 ∙ Status LEDsS20LP port for T2N PU245N ∙ Station number setting switches ∙ Transmission cable connectors∙ Reset switch only SN325 ∙ Loader portLS overview Menu⎯ 10 ⎯ S20LP-station specifications SpecificationsS20LP system specifications Scan transmission overview Setting the data send block by S-LS Allocation and network assignment by T-PDSSettings on T-PDS Setting for data linkageStation number setting Link PDS screen example Block Send Receive ⎯ 18 ⎯ Global ⎯ 20 ⎯ Settings on S-LS ⎯ 22 ⎯ ⎯ 23 ⎯ ⎯ 24 ⎯ ∙ Scan Access ∙ Start with Standby mode∙ Scan Transmission ∙ Message Transmission∙ Target Scan Time Data linkage example ∙ Settings on T-PDS Setting on S-LS LS setting screen 2 for STN #2 Cable connections RAS function Behavior in trouble∙ Station down ∙ Transmission cable breakageDuring operation Self-diagnostic functionAt initialization at power on T2N LED indicationSN325 RAS information monitored in T2N/T3H Station status Online mapStandby map Loop map Only T2NRAS information monitored on S-LS Number 1-64 on the screen shows the Station numberSelf Station Station No.01 Offline Select the Station Number Click the Status Display Possible error message are as follows Station down informationInstruction Specification Expanded data transfer instructionInstruction format FunctionParameter and construction Transfer parameter tableSample program ∙ OperationRemarks Message transmission Message transmissionComputer link protocol PC link protocol∙ Send Transfer parameters a CMDStatus B TermSTS Status Meaning Detailed Information Send completion status PC link protocol transmission Data write Transfer parametersRID Status See 7.3 5 for details on bits C, D, E, and F Important itemsXW/YW PC link protocol transmission Data read ⎯ 57 ⎯ SW067 Write enabled PC link protocol transmission program RemarksLength END Appendix Scan cycle⎯ 63 ⎯ PDS remote programming PDS Setup options screen