TABLE 11.2 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 150 kVA UPS
Block Number | Cable Size | Tightening Torque |
1 | AWG 4/0 or larger | 275 |
2 | AWG 4/0 or larger | 275 |
3 | AWG 4/0 or larger | 275 |
4 | AWG 4/0 or larger | 275 |
5 | AWG 4/0 or larger | 275 |
6 | AWG 4/0 or larger | 275 |
7 | AWG 4/0 or larger | 275 |
8 | AWG 4/0 or larger | 275 |
9 | AWG 4/0 or larger | 275 |
10 | AWG 4/0 or larger | 275 |
11 | AWG 4/0 or larger | 275 |
*12 | Two 300MCM or larger | 275 |
|
| (Terminal is bus strip) |
*13 | Two 300MCM or larger | 275 |
|
| (Terminal is bus strip) |
NOTE: Maximum cable size is 350MCM
*One battery string (see note, pg. 35, if using multiple battery strings)
TABLE 11.3 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 225kVA UPS
Block Number | Cable Size | Tightening Torque |
1 | Two 2/0 or larger | 275 |
2 | Two 2/0 or larger | 275 |
3 | Two 2/0 or larger | 275 |
4 | Two 2/0 or larger | 275 |
5 | Two 2/0 or larger | 275 |
6 | Two 2/0 or larger | 275 |
7 | Two 2/0 or larger | 275 |
8 | Two 2/0 or larger | 275 |
9 | Two 2/0 or larger | 275 |
10 | Two 2/0 or larger | 275 |
11 | Two 2/0 or larger | 275 |
*12 | Three 4/0 or larger | 275 |
|
| (Terminal is bus strip) |
*13 | Three 4/0 or larger | 275 |
|
| (Terminal is bus strip) |
NOTE: Maximum cable size is 600MCM
*One battery string (see note, pg. 35, if using multiple battery strings)
G8000 Series Installation and Operation Manual | 31 |