14.3 Startup Procedures
The procedure to start the UPS is shown in Steps | LED Key | |||||||
|
|
|
|
|
|
|
| - LED Off |
|
|
|
|
|
|
|
| - LED On |
|
|
|
|
|
|
|
| - LED Flash |
STEP 1
Turn on the control power supply switch. (Figure 14.1) and ensure the operation lock is set to OPERATION. (Figure 13.1 - 1)
AC INPUT
BATTERIES
BYPASS INPUT
SYSTEM INITIALIZE
| UPS |
CONVERTER | INVERTER |
FLOAT CHARGE | AC |
EQUAL CHARGE | |
DISCHARGE | SWITCH |
BYPASS
AC OUTPUT
STEP 2
Wait for a few seconds.
AC INPUT
BATTERIES
BYPASS INPUT
BYPASS
PRESS ‘RUN’ SWITCH
| UPS |
CONVERTER | INVERTER |
FLOAT CHARGE | AC |
EQUAL CHARGE | |
DISCHARGE | SWITCH |
BYPASS
AC OUTPUT
STEP 3
Press the “RUN” button for at least 0.5 seconds.
CONVERTER LED is “ON” and INVERTER LED flashes.
AC INPUT
BATTERIES
BYPASS INPUT
BYPASS
UPS STARTING
WAIT FOR A WHILE
| UPS |
|
CONVERTER | INVERTER |
|
FLOAT CHARGE | AC |
|
EQUAL CHARGE |
| |
DISCHARGE | SWITCH | AC OUTPUT |
|
BYPASS
56 | G8000 Series Installation and Operation Manual |