12.2Mechanical Specification (cont.)
Rated Capacity | 150 kVA | 225 kVA | 300 kVA | |
Cabinet |
|
|
| |
Protection |
| IEC298 IP20* |
| |
Conformity |
|
|
| |
Exterior Paint | Sherwin Williams, | |||
| FRONT: 1/16 in. (1.6 mm) | |||
Panel Thickness | BACK/SIDE/TOP: 3/64 in. (1.2 mm) | |||
| BOTTOM: 1/8 in. (3.2 mm) | |||
Input/Output | TOP and BOTTOM | TOP | ||
Cabling Entrance | ||||
|
|
| ||
Ground/Control | TOP and BOTTOM | TOP | ||
Wiring Entrance | ||||
|
|
| ||
Clearance |
|
|
| |
|
|
| W: 76.8 in. | |
| W: 55.1 in. (1,400 mm) | (1,951 mm) | ||
Outline | D: 31.8 in. | |||
D: 31.8 in. (808 mm) | ||||
Dimension | (808 mm) | |||
H: 79.2 in. (2,012 mm) | ||||
| H: 79.4 in. | |||
|
|
| ||
|
|
| (2,017 mm) | |
Unit Weight | 2,600 lbs (1,180 kg) | 3,300 lbs (1,500 kg) | 4,850 lbs (2,205 kg) | |
Shipping Weight | 2,689 lbs (1,220 kg) | 3,389 lbs (1,538 kg) | 5,000 lbs (2,273 kg) | |
Floor Loading | 3,280 lbs/ft2 | 4,134 lbs/ft2 | 2,608 lbs/ft2 | |
Per Footprint | (16,014 kg/m2) | (20,184 kg/m2) | (12,733 kg/m2) | |
| FRONT: 43 7/16 in. (1,100 mm) | |||
Clearance | BACK/SIDE: 0 in. (0 mm) | |||
| TOP: 15 3/4 in. (400 mm) | |||
Heat Rejection | 35,635 BTU/h | 46,268 BTU/h | 61,690 BTU/h | |
(8,980 kcal/h) | (11,659 kcal/h) | (15,546 kcal/h) | ||
|
*IP20: Foreign objects that are 12mm (15/32”) or larger are prevented from entering the enclosure of the UPS.
44 | G8000 Series Installation and Operation Manual |