12.3Electrical Specification
warning
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if untrained personnel open the front cover.
AC Input Rated Capacity | 100 kVA (80 kW) | 150 kVA (120 kW) | 225 kVA (180kW) | 300 kVA (240 kW) |
Input Voltage |
| 480 V ( +10% to |
| |
Input Frequency |
| 60 Hz ±5% |
| |
Input Power Factor |
| 0.95 – 1.00 Lagging ( at 100% Load ) |
| |
Current Harmonic Distortion |
| 4% Maximum ( at 100% Load ) |
| |
Input Capacity Required | 107 kVA | 154 kVA | 232 kVA | 309 kVA |
Circuit Breaker Rating At 480V | 150 A Trip | 225 A Trip | 350 A Trip | 500 A Trip |
Input |
|
|
|
|
DC Input Rated Capacity | 100 kVA (80 kW) | 150 kVA (120 kW) | 225 kVA (180 kW) | 300 kVA (240 kW) |
Voltage Window |
| 288 – 414 V |
| |
Recharge Voltage Regulation |
| ± 1.5% |
| |
|
|
|
|
|
AC Output Rated Capacity | 100 kVA (80 kW) | 150 kVA (120 kW) | 225 kVA (180 kW) | 300 kVA (240 kW) |
Output Voltage |
| 480/277 V ± 1%, |
| |
Output Power Factor |
| 0.8 Lagging |
| |
Voltage Distortion | 3% with 100% Linear Load / 5% with | |||
Transient Voltage Regulation |
| < ± 2% |
| |
Transient Settling Time |
| < 50 ms |
| |
Crest Factor |
| < 2.0 |
| |
Output Frequency |
| 60 Hz ± 0.01% ( at |
| |
Synchronous Window To Utility Line |
| 59 Hz – 61 Hz |
| |
Frequency Slew Rate |
| 1 Hz/Sec |
| |
Over Load Rating |