Toshiba G8000 operation manual Environment standard, Installation Precautions

Page 19

TABLE 5.1 - UPS INSTALLATION ENVIRONMENT STANDARDS

Item

Environment standard

 

Installation Location

Indoors

 

 

Minimum operating temperature: 32 °F (0 °C)

Ambient

Maximum operating temperature: 104 °F (40 °C) (UPS only)

Temperature

Maximum operating temperature: 95 °F (35 °C) (UPS with battery system)

 

Average 24-hour operating temperature: 41 – 95 °F (5 – 35 °C).

Relative Humidity

The relative humidity must be between 30 and 90% noncondensing due to

temperature changes.

 

 

 

 

These specifications are for altitudes up to 3240 ft. (1000m) above sea level.

Altitude

Consult with the factory to determine the derating factor for installations above

 

3240 ft. (1000m).

 

 

Installation environment must not have vibration frequencies 10 Hz – 20 Hz.

Vibration and

The acceleration due to vibrations less than 10 Hz must not exceed 0.5 G.

Mechanical Shock

The acceleration due to vibrations 20 Hz – 50 Hz must not exceed 0.5 G.

 

The total amplitude due to vibrations 50 Hz – 100 Hz must not exceed 0.1 mm.

Dust

Dust must not exceed normal atmospheric levels and must not include conductive

particles, silicone or oils.

 

 

 

 

No flammable and/or explosive gas.

 

 

Hydrogen sulfide (H2S)

Less than or equal to 0.0001 PPM

 

 

 

 

Sulfurous acid gas (SO2)

Less than or equal to 0.05 PPM

 

 

 

 

Chlorine gas (Cl2)

Less than or equal to 0.002 PPM

Flammable Gas

 

 

Ammonia gas (NH3)

Less than or equal to 0.1 PPM

 

Nitrous acid gas (NO2)

Less than or equal to 0.02 PPM

 

 

 

 

Nitrous oxides (NOx)

Less than or equal to 0.02 PPM

 

Ozone (O3)

Less than or equal to 0.002 PPM

 

Hydrochloric acid mist (HCl)

Less than or equal to 0.1 mg/m3

Installation Precautions

1)Install the unit in a stable, level and upright position that is free of excessive vibration.

2)Install the unit where the ambient temperature is within the specified range.

3)DO NOT install the UPS in areas that are subject to high humidity.

4)DO NOT install the UPS in areas that allow exposure to direct sunlight.

5)DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or flammable gases.

6)DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground will reduce the effects of electrical noise and will reduce the potential for electrical shock.

7)The UPS generates and can radiate radio-frequency energy during operation. Although

RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by. If such interference is experienced, the UPS should be installed further away from the affected equipment

G8000 Series Installation and Operation Manual

11

Image 19
Contents G8000 Series Page Document November Qualified Personnel only Uninterruptible Power System UPS Toshiba International Corporation PurposeToshiba’s Customer Support Center Toshiba Customer Support CenterTable of Contents 11.3 Introduction Symbols General Safety InstructionsProhibited Symbol indicates do not take action Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsDo not tilt the UPS more than 10 from upright position General MaintenanceKeep the area arround the UPS clean Transporting/UnpackingAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Install the UPS in a controlled environment Installation PrecautionsKeep the Specified Clearance around the UPS Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Follow the torque criteria for tightening screws Wiring/ConnectionPerform wiring and connections with correct polarity Connect only one 1 ground wire to the earth ground terminalFor 100, 150, 225KVA GND 150/225 kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions300 kVA UPS Exterior Dimensions Inches Transporting 8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Qualified Personnel only Maintenance PrecautionsQualified Personnel shall Do not dispose of the batteries in a fire DisposalDo not open or mutilate the batteries Installation UPS Clearance UnpackingAnchor Bolts Anchor Bolt Installation DetailExternal Wiring Diagram UPS WiringBlock Number Cable Size Tightening Torque Terminal Blocks and Power CablesRecommended Cable Size & Tightening Torque for 150 kVA UPS AC Input Bypass AC Output Battery Control Wires CRA-1/OL Plate #4 Terminal Bus # Recommendation Bus Number Cable Size Tightening TorqueExternal Breakers Grounding WireBe sure to ground the UPS as specified G8000 100 kVA G8000 150/225 kVA Signal Name Operation Control Wires10 Connection Between UPS, Battery Cabinet & Bypass Breaker 11 Grounding Configuration with Input Neutral Grounded Grounding ConfigurationRecommended Configuration for delta-input Grounding Configuration without input neutral15 Grounding Configuration with CORNER-GROUNDED DELTA-INPUT Grounding Configuration with corner-grounded delta-inputTerms Specification Remarks UPS SpecificationsGeneral Specification Mechanical SpecificationRated Capacity 150 kVA 225 kVA 300 kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD Indicators50% Normal DisplayAC-VO AC- I O 50% Volt Freq .0Hz32TIM AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz DC-V BATT-V BATT- I 0A09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesPre-operational Check Operation TypesPerform the pre-operational check before operating the UPS Procedure to start the UPS is shown in Steps Startup ProceduresAC Vo 480 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Equal Charge LED is on Emergency Power Off EPO TroubleshootingTypes of Errors 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesLCD Message Indication Description Button functions LCD Scroll w/ faults or warningsDo not open the front and/or rear panels Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not attempt to modify or relocate the UPSPage Page Industrial Division