Toshiba G8000 operation manual UPS Specifications, General Specification, Mechanical Specification

Page 51

12 UPS Specifications

12.1General Specification

Terms

Specification

Remarks

Conforming Standard

UL1778-2001

UL, cUL

Ambient Temperature

32 – 104 °F (0 – 40 ° C)

 

Relative Humidity

30% – 90%

Non-condensing

Altitude

< 3,280 ft (< 1,000 m)

Contact Toshiba Technical Support for

 

instalation above 3280 ft. (1000 m)

 

 

Audible Noise

68 dB(150/225 kVA), 72 dB(300 kVA)

1m (39”) away from front

Insulation Resistance

3 MΩ

With 500V-Megger

 

AC 2 kV – 1 min.

Main Circuit

Insulation Breakdown

AC 1.5 kV – 1 min.

External Interface

 

AC 500 V – 1 min.

Control Circuit

12.2Mechanical Specification

Rated Capacity

100 kVA:

100 kVA:

T80S3K10KK6XS2H

T80S3K10KK6XSNH

 

Cabinet

 

 

Protection

IEC298 IP20*

Conformity

 

 

Exterior Paint

Sherwin Williams, HHT2-7055, 079 Beige Texture

 

FRONT: 1.6 mm (1/16 in.)

Panel Thickness

BACK/SIDE/TOP: 1.2mm (3/64 in.)

 

BOTTOM: 3.2mm (1/8 in.)

Input/Output

BOTTOM

Cabling Entrance

 

 

Ground/Control

BOTTOM

Wiring Entrance

 

 

Outline

W: 36.8 in. (935 mm)

W: 55.1 in. (1,400 mm)

D: 31.8 in. (808 mm)

D: 31.8 in. (808 mm)

Dimension

H: 79.2 in. (2,012 mm)

H: 79.2 in. (2,012 mm)

 

Unit Weight

1,800 lbs (816 kg)

2,500 lbs (1,134 kg)

Shipping Weight

1,850 lbs (840 kg)

2,589 lbs (1,174 kg)

Floor Loading

2,256 lbs/ft2

15,298 kg/m2

Per Footprint

(11,014 kg/m2)

(3,133 lbs/ft2)

 

FRONT: 43 7/16 in. (1,100 mm)

Clearance

BACK/SIDE: 0 in. (0 mm)

 

TOP: 15 3/4 in. (400 mm)

Heat Rejection

27,620 BTU/h

(6,960 kcal/h)

 

*IP20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UPS.

G8000 Series Installation and Operation Manual

43

Image 51
Contents G8000 Series Page Document November Qualified Personnel only Uninterruptible Power System UPS Toshiba International Corporation PurposeToshiba’s Customer Support Center Toshiba Customer Support CenterTable of Contents 11.3 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsDo not tilt the UPS more than 10 from upright position General MaintenanceKeep the area arround the UPS clean Transporting/UnpackingAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Follow the torque criteria for tightening screws Wiring/ConnectionPerform wiring and connections with correct polarity Connect only one 1 ground wire to the earth ground terminalFor 100, 150, 225KVA GND 150/225 kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions300 kVA UPS Exterior Dimensions Inches Transporting 8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation UPS Clearance UnpackingAnchor Bolts Anchor Bolt Installation DetailExternal Wiring Diagram UPS WiringBlock Number Cable Size Tightening Torque Terminal Blocks and Power CablesRecommended Cable Size & Tightening Torque for 150 kVA UPS AC Input Bypass AC Output Battery Control Wires CRA-1/OL Plate #4 Terminal Bus # Recommendation Bus Number Cable Size Tightening TorqueGrounding Wire External BreakersBe sure to ground the UPS as specified G8000 100 kVA G8000 150/225 kVA Signal Name Operation Control Wires10 Connection Between UPS, Battery Cabinet & Bypass Breaker 11 Grounding Configuration with Input Neutral Grounded Grounding ConfigurationRecommended Configuration for delta-input Grounding Configuration without input neutral15 Grounding Configuration with CORNER-GROUNDED DELTA-INPUT Grounding Configuration with corner-grounded delta-inputTerms Specification Remarks UPS SpecificationsGeneral Specification Mechanical SpecificationRated Capacity 150 kVA 225 kVA 300 kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD Indicators50% Normal DisplayAC-VO AC- I O 50% Volt Freq .0Hz32TIM AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz DC-V BATT-V BATT- I 0A09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Procedure to start the UPS is shown in Steps Startup ProceduresAC Vo 480 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Equal Charge LED is on Troubleshooting Emergency Power Off EPOTypes of Errors 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesLCD Message Indication Description Button functions LCD Scroll w/ faults or warningsDo not open the front and/or rear panels Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not attempt to modify or relocate the UPSPage Page Industrial Division