Toshiba G8000 operation manual CRA-1/OL

Page 41

If your system is equiped with bus strip terminals for the A/C INPUT, BYPASS INPUT, A/C OUTPUT and BATTERY connections, Toshiba recommends using the compression lugs listed in Table 11.4, or their equivalent, for cable terminations for mounting on the bus strip.

5.3 in. (135 mm)

1.97 in.

1.77 in.

(50 mm)

(45 mm)

 

 

 

 

 

 

 

 

 

 

1.75 in.

(45 mm)

3in.

(77 mm)

FIGURE 11.6 - TERMINAL BUS Detail

table 11.4 Recommended crimp type compression lugs for Bus Strip Terminals

Wire Size

Wire

Recommendation

Crimp tool Required

 

Strand

 

 

Burndy type Y35 or Y46

 

Class

Vendor

Cat. No.

Color Key

Die Index

1/0

B

Burndy

YA25

Pink

12 / 348

 

I

Ilsco

CRA-1/OL

Pink

12 / 348

 

B

Burndy

YA25-LB

Black

13

2/0

B

Burndy

YA26

Black

13

 

I

Ilsco

CRA-2/OL

Black

13

 

B

Burndy

YA27-LB

Orange

14 / 101

3/0

B

Burndy

YA-27

Orange

14 / 101

 

I

Ilsco

CRB-3/OL

Orange

14 / 101

 

B

Burndy

YA28-LB

Purple

15

4/0

B

Burndy

YA28

Purple

15

 

I

Ilsco

CRB-4/OL

Purple

15

 

B

Burndy

YA29-LB

Yellow

16

300 MCM

B

Burndy

YA30

White

17 / 298

 

I

Ilsco

CRA-30OL

White

17 / 298

 

B

Burndy

YA32-LB

Red

18 / 324

350 MCM

B

Burndy

YA31L

Red

18

 

I

Ilsco

CRA-350

Red

18

600 MCM

B

Burndy

YA36L

Green

22

 

I

Ilsco

CRA-600

Green

22

G8000 Series Installation and Operation Manual

33

Image 41
Contents G8000 Series Page Document November Qualified Personnel only Uninterruptible Power System UPS Toshiba’s Customer Support Center PurposeToshiba Customer Support Center Toshiba International CorporationTable of Contents 11.3 Introduction Prohibited Symbol indicates do not take action General Safety InstructionsSymbols Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsKeep the area arround the UPS clean General MaintenanceTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Keep the Specified Clearance around the UPS Installation PrecautionsInstall the UPS in a controlled environment Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Perform wiring and connections with correct polarity Wiring/ConnectionConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screwsFor 100, 150, 225KVA GND 150/225 kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions300 kVA UPS Exterior Dimensions Inches Transporting 8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Qualified Personnel shall Maintenance PrecautionsQualified Personnel only Do not open or mutilate the batteries DisposalDo not dispose of the batteries in a fire Installation UPS Clearance UnpackingAnchor Bolts Anchor Bolt Installation DetailExternal Wiring Diagram UPS WiringBlock Number Cable Size Tightening Torque Terminal Blocks and Power CablesRecommended Cable Size & Tightening Torque for 150 kVA UPS AC Input Bypass AC Output Battery Control Wires CRA-1/OL Plate #4 Terminal Bus # Recommendation Bus Number Cable Size Tightening TorqueBe sure to ground the UPS as specified Grounding WireExternal Breakers G8000 100 kVA G8000 150/225 kVA Signal Name Operation Control Wires10 Connection Between UPS, Battery Cabinet & Bypass Breaker 11 Grounding Configuration with Input Neutral Grounded Grounding ConfigurationRecommended Configuration for delta-input Grounding Configuration without input neutral15 Grounding Configuration with CORNER-GROUNDED DELTA-INPUT Grounding Configuration with corner-grounded delta-inputGeneral Specification UPS SpecificationsMechanical Specification Terms Specification RemarksRated Capacity 150 kVA 225 kVA 300 kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD IndicatorsAC-VO AC- I O 50% Normal DisplayVolt Freq .0Hz 50%BYP I/P-V Freq .0Hz AC I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIM09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesPerform the pre-operational check before operating the UPS Operation TypesPre-operational Check Procedure to start the UPS is shown in Steps Startup ProceduresAC Vo 480 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Equal Charge LED is on Types of Errors TroubleshootingEmergency Power Off EPO 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesLCD Message Indication Description Button functions LCD Scroll w/ faults or warningsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPage Page Industrial Division