Toshiba 300, 500 KW, 480 V, 125 operation manual 56875FOR80,100,100,150,150,225KVAKVA

Page 24
PN 40830

6 Warning Labels

Below are representative warning labels and their location on the UPS. Exterior Handling labels shown in section 4.3, Transporting/Unpacking, are in the manual packet, and attached to the UPS shipping cover- ing and shipping pallet.

NOTICE

Make sure all the warning labels are installed in the appropriate locations.

If a label is missing or illegible, contact Toshiba Customer Support Center or an authorized representative.

(A) 48082

DANGER

AC VOLTAGE

This UPS receives power from more than one source. Disconnect all AC sources before performing any service or testing inside this unit

48082

(C) 56875FOR80,100,100,150,150,225KVAKVA

USE COPPER CONDUCTORS ONLY!

REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE

1

2

 

3

 

4

5

 

6

7

 

8

9

 

10

11

 

12

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U

V

 

W

U

V

 

W

N

 

U

V

 

W

N

-

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480 V

 

 

 

 

 

480V

 

 

 

 

 

480V

 

 

 

 

400V

 

 

AC INPUT

 

 

 

 

BYPASS INPUT

 

 

 

 

AC OUTPUT

 

 

 

BATTERY

(C) 58708 FOR 300KVA

USE COPPER CONDUCTORS ONLY !

REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE

 

1

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

11

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U

V

 

W

-

 

+

U

V

 

W

 

N

U

 

V

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58708

 

 

480V

 

 

 

 

400V

 

 

 

480V

 

 

 

480V

 

 

 

 

AC INPUT

 

 

 

BATTERY

 

 

BYPASS INPUT

 

 

AC OUTPUT

 

 

(B) 40308

DANGER

HAZARDOUS VOLTAGES Hazardous voltages are used in the operation

of this equipment and could cause severe personal injury or loss of life.

The following precautions should be observed to reduce the risk of injury or death.

Only qualified technicians familiar with this equipment and the information supplied with it should be permitted to install and operate this equipment.

Installation of electrical equipment must be done in accordance with National Electrical Code and any other state or local codes. Proper grounding and conductor sizing must be installed for safe operation.

During operation, keep all covers in place and cabinet doors shut.

When performing visual inspections and maintenance, if possible, be sure the UPS is turned off and the incoming AC feed is turned off and locked out.

The UPS and Battery Cabinet will have hazardous voltages present even after the AC feed is turned off.

If it is necessary to make measurements with the power on, do not touch any electrical connection points. Remove all jewelry from wrists and fingers. Make sure test equipment is in good, safe operating condition.

While servicing, stand on some type of insulation, and be sure not to be grounded.

Follow the safety instructions given in the equipment manual carefully and observe all danger, warning and caution notices.

40308

(D) 40830

WA RN I N G

CRITICAL FUSE SIZING

Incorrect fuse replacement size may result in fire or inadequate equipment protection.

Replace only with same type and rating of fuse.

14

G8000 Series Installation and Operation Manual

Image 24
Contents G8000 Series Page Document April Qualified Personnel only Uninterruptible Power System UPS Purpose Toshiba’s Customer Support CenterToshiba Customer Support Center Toshiba International CorporationTable of Contents 11.4 Iii 101105 Page Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerGeneral Maintenance Keep the area arround the UPS cleanTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsEnvironment standard Metal Conduit is not AN Acceptable Ground Conductor Routing and GroundingWiring/Connection Perform wiring and connections with correct polarityConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screws56875FOR80,100,100,150,150,225KVAKVA GND 150/225 KVA UPS Warning Labels 500 KVA UPS Warning Labels Weight and Dimensions Model Unit ShippingTransporting Transporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting 80-300 KVA UPS by Forklift500 kVA Operating Precautions Storage/Operating EnvironmentPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolts 150/225 kVA300 kVA 80/100/125 kVAUPS Wiring Single Input External Wiring DiagramOutput 3φ4W 11.1 80/100/125 kVA Terminal Blocks and Power Cables Copper WireBlock Number Cable Size Min-Max Tightening TorqueBlock Number Cable Size Min-Max Tightening Torque AC Output Battery Phase AC Power Lugs Phase Neutral Battery DC Power Lugs Terminal Buss Details for 500KVA UPSCRA-1/OL Block Number Cable Size Min-Max Tightening Torque2 AWG 2/0 300 in.-lb .9 NmBus Number Cable Size Min-Max Tightening Torque2Torque1 UPS Power Cable Conduit Landing Plates Front of UPS11 TOP Access Conduit Landing Plate 150 and 225 KVA only 12 TOP Access Conduit Landing Plates 300 KVA Grounding Wire External BreakersDC I nput Be sure to ground the UPS as specifiedG8000 80/100 kVA G8000 300 kVA Control Wires Signal Name OperationGrounding Configuration TB13φ 3φ Grounding Configuration without input neutral Recommended Configuration for delta-inputGrounding Configuration with corner-grounded delta-input 20 Grounding Configuration with CORNER-GROUNDED DELTA-INPUTUPS Specifications Specification Table G8000 Specifications Model NumberBattery InputG8000 Specifications Model Number OutputReliabil Ity EnvironConfig ContMonitor IngTypical Efficiency vs. Load Efficiency at Percent Full Load25% 50% 75% 100% Operator Interface Name FunctionKey-Switch and Buttons Graphic Display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic Display Panel LCD/LED IndicatorsLCD Indicators Name DescriptionNormal Display AC-VO AC- I O 50%Volt Freq .0Hz 50%AC I/P-V Freq .0Hz BYP I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEPO and Control Power Supply Operating Switches Operating the UPSOperation Types Pre-operational CheckOperation Description Perform the pre-operational check before operating the UPSStartup Procedures Procedure to start the UPS is shown in StepsAC Vo 480 AC Io 50% Switch Power Supply UPS to Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Equal Charge LED is on Troubleshooting Emergency Power Off EPOTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages LCD Message Indication DescriptionLCD Message Indication Description LCD Scroll w/ faults or warnings Name FunctionContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPeriodic Maintenance/Parts Replacement Scheduled MaintenanceParts Replacement Page Appendix a Installation Planning Guides Primary AC Input 480V 3-Phase / 3-WireAlternate Bypass AC Input 480V 3-Phase / 4-Wire General Mechanical InformationG8000 80kVA UPS Cabling Connection Dimensions Toshiba G8000 Series UPS Installation Planning Guide for 100kVA UPS 100kVA IPGG8000 100KVA Outline Drawing Toshiba G8000 Series UPS Installation Planning Guide for 125kVA UPS 125kVA IPGToshiba G8000 Series UPS Toshiba G8000 Series UPS Installation Planning Guide for 150kVA UPS 150kVA IPGFront Toshiba G8000 Series UPS Installation Planning Guide for 225kVA UPS 225kVA IPGFront G8000 225 KVA Outline Drawing Toshiba G8000 Series UPS Installation Planning Guide for 300kVA UPS 300kVA IPGToshiba G8000 Series UPS Toshiba G8000 Series UPS Installation Planning Guide for 500kVA UPS 500kVA IPGInstallation Planning Guide for 500kVA UPS Toshiba G8000 Series UPS 100 Appendix B Outline Drawings 101102 Figure B.2 G8000 150/225 KVA Outline Drawing103 Figure B.3 G8000 300 KVA Outline Drawing104 Figure B.4 G8000 500 KVA Outline DrawingLeave a gap of 0.25-0.30 between the cabinets. See FIG 105Insert Belleville washer between flat washer and nut 106107 BUS RAL Neut 108Page Industrial Division
Related manuals
Manual 228 pages 23.75 Kb Manual 127 pages 22.05 Kb Manual 2 pages 13.75 Kb

480, 125, 225, 150, 480 V specifications

The Toshiba e-STUDIO120, 1510, and 150 models represent a series of multifunctional printers designed for small to medium-sized businesses that require reliable, high-quality printing, scanning, and copying solutions. These models combine advanced technologies with user-friendly features, making them ideal for a range of office environments.

One of the standout features of the e-STUDIO series is the impressive print quality. With a resolution of up to 1200 x 1200 dpi, users can expect crisp text and vibrant images, making it suitable for professional documents and marketing materials. The devices are equipped with Toshiba's proprietary image technology, ensuring that every print job meets high-quality standards.

The e-STUDIO120, 1510, and 150 models boast impressive print speeds of up to 40 pages per minute, allowing businesses to streamline workflows and increase productivity. This efficiency is complemented by a robust paper handling capacity, with a standard paper tray that can hold up to 250 sheets, expandable with additional trays for larger print jobs. These models also support automatic duplex printing, reducing paper consumption and helping organizations to adopt more environmentally friendly practices.

In terms of connectivity, these printers come equipped with USB and Ethernet ports, allowing for seamless integration into any office network. Users can also take advantage of wireless printing options through mobile devices, thanks to compatibility with Apple AirPrint, Google Cloud Print, and other mobile printing solutions. This flexibility makes it easy for employees to print from their smartphones or tablets, enhancing overall operational efficiency.

Another notable characteristic is the user-friendly interface. The color touchscreen display provides easy navigation, allowing users to access various features like copying, scanning, and faxing with minimal effort. The e-STUDIO series also includes advanced security features that protect sensitive data and ensure confidential information remains secure.

The devices are designed with durability and reliability in mind, incorporating Toshiba's long-lasting components and low maintenance requirements. This ensures that businesses can count on their e-STUDIO printer for consistent performance over time, reducing downtime and service interruptions.

In summary, the Toshiba e-STUDIO120, 1510, and 150 models combine high-quality printing, advanced connectivity options, user-friendly interfaces, and strong security measures. These multifunctional printers are well-suited for businesses looking to enhance productivity and streamline their document management processes while maintaining professional print quality.