Toshiba 150, 500 KW, 480 V, 225, 300, 125, 100 UPS Power Cable Conduit Landing Plates, Front of UPS

Page 49

11.3UPS Power Cable Conduit Landing Plates

Cable conduit landing plates are provided at the bottom of the 80 kVA and100 kVA UPS, at the top and bottom of the 150/225 kVA UPS (Older models of the G8000 150/225 kVA UPS do not come equipped with an upper conduit landing plate.), and at the top only of the 300/500kVA. The recommended conduit landing arrangements are illustrated in Figure 11.9 thru 11.13.

The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the conduit landing plates.

Recommended

Conduit Placement

Order in Top Conduit

Landing Plate

 

 

 

21.85 in.

 

 

3.37 in.

 

 

 

 

 

 

7.48in.

0.78in.

AC

BYPASS

AC OUT-

BATTERY

4.74in.

 

 

 

 

 

INPUT

PUT

 

 

 

 

 

 

 

 

 

0.78 in.

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

23.74 in.

 

 

 

WIRES

 

 

 

 

 

 

 

 

 

BASE PLATES - DIMENSIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS BASE

 

 

 

 

23.11 in.

BOTTOM ENTRY DIMENSIONS

5.9 in.

FRONT OF UPS

23.73 in. 5.9 in.

FIGURE 11.9 - BOTTOM CONDUIT LANDING PLATES FOR 80/100/125 KVA

G8000 Series Installation and Operation Manual

39

Image 49
Contents G8000 Series Page Document April Qualified Personnel only Uninterruptible Power System UPS Toshiba’s Customer Support Center PurposeToshiba Customer Support Center Toshiba International CorporationTable of Contents 11.4 101 Iii105 Page Introduction Symbols General Safety InstructionsProhibited Symbol indicates do not take action Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsKeep the area arround the UPS clean General MaintenanceTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Install the UPS in a controlled environment Installation PrecautionsKeep the Specified Clearance around the UPS Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Conductor Routing and Grounding Metal Conduit is not AN Acceptable GroundPerform wiring and connections with correct polarity Wiring/ConnectionConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screws56875FOR80,100,100,150,150,225KVAKVA GND 150/225 KVA UPS Warning Labels 500 KVA UPS Warning Labels Model Unit Shipping Weight and DimensionsTransporting 8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting 80-300 KVA UPS by Forklift Transporting By Forklift500 kVA Storage/Operating Environment Operating PrecautionsPage Qualified Personnel only Maintenance PrecautionsQualified Personnel shall Do not dispose of the batteries in a fire DisposalDo not open or mutilate the batteries Installation UPS Clearance Unpacking150/225 kVA Anchor Bolts300 kVA 80/100/125 kVASingle Input External Wiring Diagram UPS WiringOutput 3φ4W Copper Wire 11.1 80/100/125 kVA Terminal Blocks and Power CablesBlock Number Cable Size Min-Max Tightening TorqueBlock Number Cable Size Min-Max Tightening Torque AC Output Battery Terminal Buss Details for 500KVA UPS Phase AC Power Lugs Phase Neutral Battery DC Power LugsCRA-1/OL AWG 2/0 300 in.-lb .9 Nm Block Number Cable Size Min-Max Tightening Torque2Torque2 Bus Number Cable Size Min-Max TighteningTorque1 Front of UPS UPS Power Cable Conduit Landing Plates11 TOP Access Conduit Landing Plate 150 and 225 KVA only 12 TOP Access Conduit Landing Plates 300 KVA External Breakers Grounding WireDC I nput Be sure to ground the UPS as specifiedG8000 80/100 kVA G8000 300 kVA Signal Name Operation Control WiresTB1 Grounding Configuration3φ 3φ Recommended Configuration for delta-input Grounding Configuration without input neutral20 Grounding Configuration with CORNER-GROUNDED DELTA-INPUT Grounding Configuration with corner-grounded delta-inputSpecification Table G8000 Specifications Model Number UPS SpecificationsBattery InputOutput G8000 Specifications Model NumberReliabil Ity EnvironCont ConfigMonitor IngEfficiency at Percent Full Load Typical Efficiency vs. Load25% 50% 75% 100% Name Function Operator InterfaceGraphic Display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic Display Panel LCD/LED Indicators 13.2 LCD/LED IndicatorsName Description LCD IndicatorsAC-VO AC- I O 50% Normal DisplayVolt Freq .0Hz 50%BYP I/P-V Freq .0Hz AC I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIM09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS EPO and Control Power Supply Operating SwitchesPre-operational Check Operation TypesOperation Description Perform the pre-operational check before operating the UPSProcedure to start the UPS is shown in Steps Startup ProceduresAC Vo 480 AC Io 50% Bypass LED is on Switch Power Supply UPS to BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Equal Charge LED is on Emergency Power Off EPO TroubleshootingTypes of Errors 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysLCD Message Indication Description Fault MessagesLCD Message Indication Description Name Function LCD Scroll w/ faults or warningsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsScheduled Maintenance Periodic Maintenance/Parts ReplacementParts Replacement Page Primary AC Input 480V 3-Phase / 3-Wire Appendix a Installation Planning GuidesAlternate Bypass AC Input 480V 3-Phase / 4-Wire General Mechanical InformationG8000 80kVA UPS Cabling Connection Dimensions Toshiba G8000 Series UPS 100kVA IPG Installation Planning Guide for 100kVA UPSG8000 100KVA Outline Drawing Toshiba G8000 Series UPS 125kVA IPG Installation Planning Guide for 125kVA UPSToshiba G8000 Series UPS Toshiba G8000 Series UPS 150kVA IPG Installation Planning Guide for 150kVA UPSFront Toshiba G8000 Series UPS 225kVA IPG Installation Planning Guide for 225kVA UPSFront G8000 225 KVA Outline Drawing Toshiba G8000 Series UPS 300kVA IPG Installation Planning Guide for 300kVA UPSToshiba G8000 Series UPS Toshiba G8000 Series UPS 500kVA IPG Installation Planning Guide for 500kVA UPSInstallation Planning Guide for 500kVA UPS Toshiba G8000 Series UPS 100 101 Appendix B Outline DrawingsFigure B.2 G8000 150/225 KVA Outline Drawing 102Figure B.3 G8000 300 KVA Outline Drawing 103Figure B.4 G8000 500 KVA Outline Drawing 104105 Leave a gap of 0.25-0.30 between the cabinets. See FIG106 Insert Belleville washer between flat washer and nut107 108 BUS RAL NeutPage Industrial Division
Related manuals
Manual 228 pages 23.75 Kb Manual 127 pages 22.05 Kb Manual 2 pages 13.75 Kb

480, 125, 225, 150, 480 V specifications

The Toshiba e-STUDIO120, 1510, and 150 models represent a series of multifunctional printers designed for small to medium-sized businesses that require reliable, high-quality printing, scanning, and copying solutions. These models combine advanced technologies with user-friendly features, making them ideal for a range of office environments.

One of the standout features of the e-STUDIO series is the impressive print quality. With a resolution of up to 1200 x 1200 dpi, users can expect crisp text and vibrant images, making it suitable for professional documents and marketing materials. The devices are equipped with Toshiba's proprietary image technology, ensuring that every print job meets high-quality standards.

The e-STUDIO120, 1510, and 150 models boast impressive print speeds of up to 40 pages per minute, allowing businesses to streamline workflows and increase productivity. This efficiency is complemented by a robust paper handling capacity, with a standard paper tray that can hold up to 250 sheets, expandable with additional trays for larger print jobs. These models also support automatic duplex printing, reducing paper consumption and helping organizations to adopt more environmentally friendly practices.

In terms of connectivity, these printers come equipped with USB and Ethernet ports, allowing for seamless integration into any office network. Users can also take advantage of wireless printing options through mobile devices, thanks to compatibility with Apple AirPrint, Google Cloud Print, and other mobile printing solutions. This flexibility makes it easy for employees to print from their smartphones or tablets, enhancing overall operational efficiency.

Another notable characteristic is the user-friendly interface. The color touchscreen display provides easy navigation, allowing users to access various features like copying, scanning, and faxing with minimal effort. The e-STUDIO series also includes advanced security features that protect sensitive data and ensure confidential information remains secure.

The devices are designed with durability and reliability in mind, incorporating Toshiba's long-lasting components and low maintenance requirements. This ensures that businesses can count on their e-STUDIO printer for consistent performance over time, reducing downtime and service interruptions.

In summary, the Toshiba e-STUDIO120, 1510, and 150 models combine high-quality printing, advanced connectivity options, user-friendly interfaces, and strong security measures. These multifunctional printers are well-suited for businesses looking to enhance productivity and streamline their document management processes while maintaining professional print quality.