Toshiba 1700 user manual Battery Backup Time, Load Shed Function, Battery Recharge Time, Fan Speed

Page 15

TOSHIBA

Battery Backup Time

The exact amount of backup time provided will vary depending on the UPS model being used, number of batteries, condition of the batteries and other factors. However, the chart below gives the times that can be expected from the standard units with batteries in good condition. For greater backup time, an additional battery module may be added to the standard unit. Only one additional battery module may be added to the standard unit. For longer runtime options contact your Toshiba sales representative or the Toshiba marketing department at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com.

Table 1

Backup Time*

UPS Model

With 1 Battery Module

With 2 Battery Modules

Full Load / Half Load

Full Load / Half Load

 

 

 

 

2000 VA

10 min / 25 min

25 min / 60 min

 

 

 

2400 VA

7 min / 20 min

23 min / 50 min

 

 

 

*Times given are approximate and will vary depending on the age of the batteries, the battery temperature, the number of previous discharges and the type of load.

Load Shed Function

The 1700 Series includes a load shed function. During battery backup operation, this function allows the load connected to two of the receptacles (figure 1, page 9) to be turned off in an effort to conserve power for more critical loads. The battery level at which these two receptacles will be turned off, or “shed”, can be set by the user (see “The Function Control Button”, page 16). By default, this feature is configured so that these two receptacles will remain on for the full battery backup time available (no “shedding”)

Battery Recharge Time

The following table gives estimates on time required to recharge the UPS’s batteries. The recharge time may vary depending on the battery temperature, the age of the batteries, and other factors.

Table 2

Battery Recharge Time*

Unit

With 1 Battery Module

With 2 Battery Modules

 

 

 

2000 VA

3 ½ hours

7 hours

 

 

 

2400 VA

3 ½ hours

7 hours

 

 

 

* Recharge times are to 90% full capacity.

Fan Speed

The 1700 Series Rackmount UPS has variable speed fans. The fan speed will vary depending on a number of factors. As the load

15

Image 15
Contents Series Toshiba Important Notice Table of Contents General Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Inspection of the New UPS Equipment Inspection/InstallationInstallation Precautions Operating PrecautionsElectronics Module External LayoutBattery Module UPS ConnectionsStandard Module Connections Starting the UPS System Starting When AC Power is AvailableOperating the UPS Display Panel LayoutStopping the UPS Starting on DC PowerUPS Display Status and Operating Condition Parallel On Line ............. On Alarm will Fan Speed Battery Backup TimeBattery Recharge Time Load Shed FunctionFunction Control Button Battery Check FunctionToshiba Toshiba Fixed Frequency Mode Troubleshooting Communication InterfaceDry Contacts RS-232C Option Card Slot Low Battery Alarm will Battery Over Heat Input Alarm will Shutdown Backup.............. On Alarm FaultsDC Bus Over Voltage Imbalance Output Under Output Over 100% ................ On Voltage Alarm will Avoid Storage of UPS EquipmentPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceParts Replacement UF1A1A020C6RK UF1A1A024C6RK Appendix a SpecificationsAppendix B Fan Speed Control Appendix C System Overload Rating Appendix D Parallel Operation Appendix E Bypass Undervoltage / Overvoltage Appendix G Weights and Dimensions Limitations and Exclusions Procedure Toshiba Toshiba Toshiba International Corporation