Warning | Display State | LED State | Alarm State | Description and Resolution |
Low Battery | Warning/Fault ... Flash | Alarm will | The batteries have less than | |
| Backup.............. Flash | sound for | 30% power remaining. The | |
|
| warning will continue until either | ||
|
| the batteries become completely | ||
|
| at 5- | ||
|
| exhausted or AC input power is | ||
|
| second | ||
|
| restored. | ||
|
| intervals. | ||
|
|
| ||
|
|
|
| |
Current | Warning/Fault ... Flash | Alarm will | An output current limit warning | |
is typically a sign of | ||||
Limit (Over | 80% .................. Flash | sound for | ||
misapplication. The load may | ||||
Current) |
| 1/2- | ||
| not be appropriate for UPS | |||
|
| second at | ||
|
| support. For further explanation | ||
|
| contact your Toshiba UPS | ||
|
| intervals. | service representative at | |
|
|
| ||
|
|
| call | |
Ambient | Warning/Fault ... Flash | Alarm will | The temperature of the UPS | |
Over Heat | 100% ................ Flash | sound for | operating environment is too | |
|
| high. Causes of this condition | ||
|
| at 15- | include allowing the room | |
|
| temperature to exceed 104°F | ||
|
| second | ||
|
| (40°C), a blocked vent or direct | ||
|
| intervals. | ||
|
| sunlight on the unit. The unit will | ||
|
|
| ||
|
|
| transfer to bypass until the | |
|
|
| temperature is reduced. |