Inspection/Installation

Inspection of the New UPS Equipment

Upon receipt of the UPS, a careful inspection for shipping damage should be made.

After Unpacking:

1)Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all original packing materials for return to shipping agent. Warranty will not apply to units damaged during shipment.

2)Check to see that the rated capacity and the model number specified on the nameplate conform to the order specifications.

Installation Precautions

CAUTION

1)Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on all sides for air ventilation and for maintenance.

2)Install the unit in a stable, level, and upright position that is free of vibration.

3)Install the unit where the ambient temperature is between 32° and 104°F (0° and 40°C).

4)Do not install the UPS in areas that are subject to high humidity.

5)Do not install the UPS in a location that will cause direct sunlight to shine on the unit.

6)Do not install the UPS in areas that are subject to contamination such as high levels of airborne dust, metal particles, or flammable gas.

7)Avoid installation near sources of electrical noise. Always make sure that the unit earth ground is intact to prevent electrical shock and to help reduce electrical noise.

8)Do not install where water or any foreign object may get inside the UPS.

9)This UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside the unit there is no guarantee that the UPS will not influence some sensitive devices which are operating close by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment.

Operating Precautions

CAUTION

1)The UPS should not be powered up until this entire manual has been reviewed.

8

Image 8
Contents Series Toshiba Important Notice Table of Contents General Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Inspection/Installation Installation PrecautionsOperating Precautions Inspection of the New UPS EquipmentExternal Layout Electronics ModuleStandard Module Connections Battery ModuleUPS Connections Starting When AC Power is Available Operating the UPSDisplay Panel Layout Starting the UPS SystemStarting on DC Power Stopping the UPSUPS Display Status and Operating Condition Parallel On Line ............. On Alarm will Battery Backup Time Battery Recharge TimeLoad Shed Function Fan SpeedBattery Check Function Function Control ButtonToshiba Toshiba Fixed Frequency Mode Dry Contacts RS-232C Option Card Slot TroubleshootingCommunication Interface Low Battery Alarm will Battery Over Heat Input Alarm will Faults Shutdown Backup.............. On AlarmDC Bus Over Voltage Imbalance Output Under Output Over 100% ................ On Voltage Alarm will Storage of UPS Equipment AvoidParts Replacement Preventive and Scheduled Maintenance/Parts ReplacementPreventive Maintenance Appendix a Specifications UF1A1A020C6RK UF1A1A024C6RKAppendix B Fan Speed Control Appendix C System Overload Rating Appendix D Parallel Operation Appendix E Bypass Undervoltage / Overvoltage Appendix G Weights and Dimensions Limitations and Exclusions Procedure Toshiba Toshiba Toshiba International Corporation