Toshiba 1700 user manual Parallel On Line ............. On Alarm will

Page 14

14

UPS Display Status and Operating Condition

Operation Mode Display State

LED State

Alarm State

Notes

Parallel

On Line ............. On

Alarm will

Parallel operation occurs when

Operation

AC Input............ On

sound for

input power is present, but

 

Battery .............. On

1 second

inadequate to fully power the

 

connected load. The batteries

 

20% to 100%*... On

at 10

 

are used to supplement the

 

*see note 1.

second

 

AC input power. The UPS will

 

 

intervals.

 

 

return to normal operation

 

 

 

 

 

 

when full input power returns.

All other display conditions constitute either a warning or a fault condition. These conditions are explained in the section titled “Troubleshooting” (page 22) in the charts on Warnings and Faults.

Note 1: The level meter, which consists of the LEDs labeled 20% through 150%, will light according to the current amount of load connected. As the load exceeds one level, the next level will begin to blink, increasing the blink rate as the load increases until that full percentage is reached. For example, if the unit is loaded to 40% of maximum output power the 20% and 40% LEDs will be lit. If another small load is added increasing the load to 45% the 60% LED will begin to blink. If a little bit more load is added so that the total load becomes 50% the 60% LED will blink faster. This will continue until enough load is added to equal 60% of the maximum output power at which time the 60% LED will stop blinking and light continuously.

Note 2: The level meter described in note 1 above also displays the remaining battery time when the unit is in backup mode. If the batteries are fully charged when the unit switches to backup mode the 20% through 100% LEDs will light. As the batteries begin to discharge, the LEDs starting from the top will blink rapidly then slowly and will then turn off as the battery time runs down. For example if the unit has been running on battery power and there is 90% battery capacity remaining the 20% through 80% LEDs will be lit and the 100% LED will be blinking.

TOSHIBA

Image 14
Contents Series Toshiba Important Notice Table of Contents General Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Operating Precautions Inspection/InstallationInstallation Precautions Inspection of the New UPS EquipmentExternal Layout Electronics ModuleStandard Module Connections Battery ModuleUPS Connections Display Panel Layout Starting When AC Power is AvailableOperating the UPS Starting the UPS SystemStarting on DC Power Stopping the UPSUPS Display Status and Operating Condition Parallel On Line ............. On Alarm will Load Shed Function Battery Backup TimeBattery Recharge Time Fan SpeedBattery Check Function Function Control ButtonToshiba Toshiba Fixed Frequency Mode Dry Contacts RS-232C Option Card Slot TroubleshootingCommunication Interface Low Battery Alarm will Battery Over Heat Input Alarm will Faults Shutdown Backup.............. On AlarmDC Bus Over Voltage Imbalance Output Under Output Over 100% ................ On Voltage Alarm will Storage of UPS Equipment AvoidParts Replacement Preventive and Scheduled Maintenance/Parts ReplacementPreventive Maintenance Appendix a Specifications UF1A1A020C6RK UF1A1A024C6RKAppendix B Fan Speed Control Appendix C System Overload Rating Appendix D Parallel Operation Appendix E Bypass Undervoltage / Overvoltage Appendix G Weights and Dimensions Limitations and Exclusions Procedure Toshiba Toshiba Toshiba International Corporation