Appendix E: Bypass Undervoltage / Overvoltage

When the 1700 Series Rackmount UPS is in bypass mode the undervoltage and overvoltage limits are restricted to +/-10% of the rated input voltage. If the input voltage is outside of this voltage window the UPS output will be turned off. There is a 5% hysteresis associated with both the upper and lower limits. This means that once output has been turned off the input voltage will have to be within ±5% of the rated input voltage before the startup sequence will reinitialize. (To start the UPS when the input power is outside of the allowable range see the section entitled “Starting on DC Power”, page 12.)

When the UPS is started, if the RUN/STOP switch is in the STOP (bypass) position the unit will start in the on-line mode for 1 second before switching to bypass mode. If the input voltage is out of range the UPS will turn off the output after 1 second rather than switching to bypass.

33

Image 33
Contents Series Toshiba Important Notice Table of Contents General Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Installation Precautions Inspection/InstallationOperating Precautions Inspection of the New UPS EquipmentElectronics Module External LayoutBattery Module UPS ConnectionsStandard Module Connections Operating the UPS Starting When AC Power is AvailableDisplay Panel Layout Starting the UPS SystemStopping the UPS Starting on DC PowerUPS Display Status and Operating Condition Parallel On Line ............. On Alarm will Battery Recharge Time Battery Backup TimeLoad Shed Function Fan SpeedFunction Control Button Battery Check FunctionToshiba Toshiba Fixed Frequency Mode Troubleshooting Communication InterfaceDry Contacts RS-232C Option Card Slot Low Battery Alarm will Battery Over Heat Input Alarm will Shutdown Backup.............. On Alarm FaultsDC Bus Over Voltage Imbalance Output Under Output Over 100% ................ On Voltage Alarm will Avoid Storage of UPS EquipmentPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceParts Replacement UF1A1A020C6RK UF1A1A024C6RK Appendix a SpecificationsAppendix B Fan Speed Control Appendix C System Overload Rating Appendix D Parallel Operation Appendix E Bypass Undervoltage / Overvoltage Appendix G Weights and Dimensions Limitations and Exclusions Procedure Toshiba Toshiba Toshiba International Corporation
Related manuals
Manual 2 pages 63.93 Kb