Siemens Server manual Ext. Reset, Inputs IN1, IN2, COM 0 W&T RS485 bus W&T RS232

Page 9

Overview of ChemWeb Server

Ext. Reset

If the reset input is connected more than 3 seconds to ground GND or the RESET key is pressed at least 3 seconds, a reset is carried out at the webserver as well as at the modem module.

Terminal No.:

Designation:

Explanation:

5

GND

Ground

6

Reset

Input for external reset of ChemWeb Server

Inputs (IN1, IN2)

The two digital inputs are fitted internally with pull-up resistors and are activated by connecting them to GND. On activation, digital input 1 (IN1) dials into the internet via the set parameters. Digital input 2 (IN2) deactivates the installed modem to enable null modem operation via COM 1.

Terminal No.:

Designation:

Explanation:

7

GND

Ground

8

IN1

Digital input 1 – Dialing into internet

9

IN2

Digital input 2 – Switching over to null modem operation

10

GND

Ground

COM 0 - W&T RS485 bus (W&T - RS232)

The serial interface is activated as RS485 port by setting a coding jumper (RS485 enable – GND). At the same time the RS232 interface via DSUB plug is switched off. Without the coding jumper this interface works as standard RS232 via the DSUB connection.

This DSUB connection must not be used in the case of RS485 operation!

Double data lines A and B are connected to the terminals so that the internally existent pull-up, pull- down and bus terminating resistors can easily be wired externally, if required.

If the ChemWeb Server is located at an end position of the RS485 bus, the terminating resistor “Termination” (11) has to be connected to A (15). If the device is coupled in the bus center, “Termination” must remain open.

At least at one point of the bus, the data lines should be connected to B by means of resistor Symm

(+) and to A by means of resistor Symm (-) in order to avoid floating of the data lines.

Terminal No.:

Designation:

Description:

MG/L 5

Connection

 

 

 

11

Termination

Bus terminating resistor (at end of RS485 bus)

-------

12

Symm (-)

Balancing resistor 1 (1 x in RS485 bus)

-------

13

Symm (+)

Balancing resistor 2 (1 x in RS485 bus)

-------

14

B

Data line B

-------

15

A

Data line A

-------

16

B

Data line B

Terminal 20

17

A

Data line A

Terminal 21

18

RS485 enable

Switchover RS485 - RS232

-------

19

GND

Ground

-------

3

Image 9
Contents ChemWeb Server Page Table of Contents Software and Firmware License Disconnect and Lockout Power Before Servicing Page Overview of ChemWeb Server Description of ChemWeb Server Power SupplyExt. Reset Inputs IN1, IN2COM 0 W&T RS485 bus W&T RS232 Ethernet / 10BaseT RJ45 COM 1 RS232 null modemTelephone line only for analog or Isdn version OutputsLED displays CompactFlash slot CFConnecting more than one ChemWeb Server Installation of RS485 busRS485 bus system 390 Ohm +/- 2 % Setting the IP address of the ChemWeb Server Network connection in a LANDirect network connection Setting the IP address of the ChemWeb Server Analog modem Isdn modem Switched connection via modemSetting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Null modem connection via serial interface Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server without Dhcp Connection via Internet Setting the IP address of the ChemWeb Server with DhcpStartup Basic settings via a BrowserServer Setup ISP configurationBus scan Mail configuration Event configuration Server commands Time/date settingChange passwords Name configuration Chip info Display and configuration window Operation and Data AccessOperation via Web Browser Navigation windowOperation and Data Access Log files 03 04 a 00.TXTBacking up log files Data access via FTPData access via Web Browser Data access to CompactFlash card with card scannerTechnical data Appendix Tested Web Browser Appendix Appendix Page Siemens All Rights Reserved