Siemens Server manual COM 1 RS232 null modem, Ethernet / 10BaseT RJ45, Outputs

Page 10

Description of ChemWeb Server

COM 1 - RS232 null modem

This RS232 port is used for modem parameterization and null modem operation without having to disconnect the device from its application environment.

Terminal No.:

Designation:

Description:

30

GND

Ground

31

CTS

RS232 signal CTS

32

RTS

RS232 signal RTS

33

RXD

RS232 signal RXD

34

TXD

RS232 signal TXD

35

GND

Ground

Ethernet / 10BaseT (RJ45)

With this connection the ChemWeb Server can be linked with 10Mbit/s to a network or directly to the network board of a PC. For connection with a network switch or hub, a standard patch cable has to be used. A direct connection to a PC network board only works when using a crossed network cable.

Telephone line (only for analog or ISDN version)

The connection to the telephone network (analog modem or ISDN) can be made either via the screw terminals or the RJ45 socket. Both connection methods are equally good.

Terminal No.:

Designation:

Description analog:

Description ISDN:

20

LA1

--

S0 bus line B2

21

LA

Telephone line A

S0 bus line B1

22

LB

Telephone line B

S0 bus line A1

23

LB1

--

S0 bus line A2

Outputs

The ChemWeb Server has two relay outputs. Relay output 1 indicates the online status of the modem, i.e.: it is activated as soon as an Internet connection exists. Relay output 2 can be activated or deactivated via page frame “Server Setup” ==> “Server Commands” by means of button “Relay 2”.

Terminal No.:

Designation:

Description:

24

REL 2

Relay 1 – make contact

25

REL 2

Relay 1 - Common

26

REL 2

Relay 1 – break contact

27

REL 1

Relay 2 – make contact

28

REL 1

Relay 2 - Common

29

REL 1

Relay 2 – break contact

The CF card must always be inserted before switching on the ChemWeb Server and must never be removed during operation! The CF card must also contain the firmware of the ChemWeb Server. It is not possible to operate the ChemWeb Server with a blank CF card!

4

Image 10
Contents ChemWeb Server Page Table of Contents Software and Firmware License Disconnect and Lockout Power Before Servicing Page Overview of ChemWeb Server Power Supply Description of ChemWeb ServerInputs IN1, IN2 Ext. ResetCOM 0 W&T RS485 bus W&T RS232 Telephone line only for analog or Isdn version COM 1 RS232 null modemEthernet / 10BaseT RJ45 OutputsCompactFlash slot CF LED displaysInstallation of RS485 bus Connecting more than one ChemWeb ServerRS485 bus system 390 Ohm +/- 2 % Network connection in a LAN Setting the IP address of the ChemWeb ServerDirect network connection Setting the IP address of the ChemWeb Server Switched connection via modem Analog modem Isdn modemSetting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Null modem connection via serial interface Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server Setting the IP address of the ChemWeb Server without Dhcp Setting the IP address of the ChemWeb Server with Dhcp Connection via InternetBasic settings via a Browser StartupISP configuration Server SetupBus scan Mail configuration Event configuration Time/date setting Server commandsChange passwords Name configuration Chip info Operation via Web Browser Operation and Data AccessDisplay and configuration window Navigation windowOperation and Data Access 03 04 a 00.TXT Log filesData access via FTP Backing up log filesData access to CompactFlash card with card scanner Data access via Web BrowserTechnical data Appendix Tested Web Browser Appendix Appendix Page Siemens All Rights Reserved