APC MX28B-1200, MX28B-2400 manual Product Overview and Technical Description

Page 13

Revision B

MX28B-1200 PRODUCT MANUAL

4. PRODUCT OVERVIEW AND TECHNICAL DESCRIPTION

4.1Description

The APC Models MX28B-1200/2400 represents a family of stand-alone -48V dc power plants. Through the use of modular power and distribution box frames, a system is configurable in such a manner that it will support most typical applications within the specified current range of up to 3600 amps without special application engineering or assistance.

The system is designed to start as a base unit capable of supplying 1200 amps of –48V dc power in a single box frame with integrated power distribution breakers and an advanced control and monitoring module. Standard distribution for a power bay includes up to 48 plug-in circuit breakers (1 to 100 amps), or large panel-mounted circuit breakers (250 to 700 amps).

Expansion of the base unit is accomplished by adding power frames and distribution frames on either side of the base unit The distribution box frames come with a variety of circuit breaker and fuse options. Power expansion of the 1200 amp plant to a 2400 amp plant only requires the addition of splice plates to the existing bus structure.

An optional low voltage disconnect (LVD) can be provided on either the battery or the load side in each power bay. Systems incorporating power distribution frames need an external LVD unit

A 1200 amp MX28B is shown in. Figure 4-1. A block diagram is shown in Figure 4–2.

Figure 4-1 MX28B-1200

MX28B-1200/2400

7

Image 13
Contents Model MX28B-1200/2400 MX28B-1200 Product Manual Revision Date Description Revision HistoryTable of Contents Product Manual Page Introduction General InformationInspection upon Receipt of Goods General Visible External DamageReturn of Damaged Goods Concealed DamageCustomer Service and Support Page Warranty Returns Warranty ProvisionsWarranty Repair or Replacement General ProvisionsMX28B-1200 Product Manual Description Product Overview and Technical DescriptionMX28B-1200 System Diagram Rectifiers Power Output CapacityControl Unit Battery connections AC Input PowerDC Distribution Mechanical EnvironmentalCompliance Page Preparation Recommended Tools Installation ProceduresRecommended Test Equipment Equipment InspectionMounting Room/LocationsTerminal Block VentilationMX28B-1200 Product Manual Connecting the Cables Battery Connections Battery DisconnectCable Sizing Considerations Multiple Frame Assembly Power Bus Connections Rectifier InstallationControl Wiring Extension Multi-Bay Wiring Diagram MX28B-1200 Product Manual Alarm Interface PC Board Alarm ConnectionsExternal Alarm Input Definition External Alarm InputsExternal Alarm Input Connections Alarm Outputs Plug-in Circuit Breakers Alarm Terminal Output Designation User Alarm Notes NO-NC-CFuse APC Part Rating 10 Fuse Bay Connections Power Distribution Fuse Load ConnectionsApply AC Power Battery Temperature Probe InstallationFull System Power Up Status Alarms System Modules Batt PIN OEMPage User Interface SETUP, ADJUSTMENTS, and OperationParameter Locations, Descriptions, and Default Values Alarm Output RelaysMX28B-1200 Product Manual Setup PIN AlarmsStatus System SET-ALMOUT-RLY RLY-MAP DateAlias IN-RLY RLY-MAPParam Modules Rect SET-ALMInfo Cirbkr SET-ALMAlias Fuse Fuse SET-ALMBatt SET-ALM LVD SET-ALMComp PIN OEMOFF APCMX28B-1200 Product Manual Rect 1ofN Alm m+ Test Relay Batt Disc Alm m+ 48V Fuse 1 Alm LVD2 LVD1MX28B-1200 Product Manual MX28B-1200 Product Manual