MX28B-1200 PRODUCT MANUAL

Revision B

5.1.5 Room/Locations

NOTE: The APC Model MX28B dc power plant is to be installed in a room, vault, or similar enclosure that is accessible only to qualified persons in accordance with the NEC or the authority having jurisdiction.

Prior to installation, drawings, floor loading requirements, external alarm points, ac service entrance, and grounding schemes should all be checked and confirmed. If batteries are to be mounted in a room separate from the power plant, careful attention should be paid to battery cable voltage drop effects. Environmental operating temperatures and ventilation/cooling considerations should also be noted, not just for the power system but for all other equipment that may reside in the power room area.

5.1.6 Mounting

The box frame housing the MX28B components is self-supporting, but designed to be bolted to the floor of the housing structure. Figure 5-1 shows the footprint of the box frame and the mounting points with dimensions (shown in inches). Consult the system design specifications to see if it is necessary to electrically isolate the frame from the floor structure. This is required in many installations.

FRONT

23.00

1.50

11.50 11.50

Figure 5-1 Floor Mounting Dimensions

Systems with multiple box frames are mounted with each frame touching, side by side. The side cover panels where two frames touch are removed so that bus work and control cables can pass between the frames. Three holes are provided in center vertical rail of each side to allow the frames to be mechanically secured to each other if desired.

14

MX28B-1200/2400

Image 20
Contents Model MX28B-1200/2400 MX28B-1200 Product Manual Revision History Revision Date DescriptionTable of Contents Product Manual Page General Information IntroductionInspection upon Receipt of Goods General Visible External DamageConcealed Damage Return of Damaged GoodsCustomer Service and Support Page Warranty Provisions Warranty ReturnsWarranty Repair or Replacement General ProvisionsMX28B-1200 Product Manual Product Overview and Technical Description DescriptionMX28B-1200 System Diagram Control Unit Power Output CapacityRectifiers DC Distribution AC Input PowerBattery connections Compliance EnvironmentalMechanical Page Installation Procedures Preparation Recommended ToolsRecommended Test Equipment Equipment InspectionRoom/Locations MountingVentilation Terminal BlockMX28B-1200 Product Manual Cable Sizing Considerations Battery Connections Battery DisconnectConnecting the Cables Rectifier Installation Multiple Frame Assembly Power Bus ConnectionsControl Wiring Extension Multi-Bay Wiring Diagram MX28B-1200 Product Manual Alarm Connections Alarm Interface PC BoardExternal Alarm Input Connections Alarm Outputs External Alarm InputsExternal Alarm Input Definition Alarm Terminal Output Designation User Alarm Notes NO-NC-C Plug-in Circuit BreakersFuse APC Part Rating Power Distribution Fuse Load Connections 10 Fuse Bay ConnectionsBattery Temperature Probe Installation Apply AC PowerStatus Alarms System Modules Batt PIN OEM Full System Power UpPage SETUP, ADJUSTMENTS, and Operation User InterfaceAlarm Output Relays Parameter Locations, Descriptions, and Default ValuesMX28B-1200 Product Manual Alarms Setup PINStatus System SET-ALMDate OUT-RLY RLY-MAPAlias IN-RLY RLY-MAPModules Rect SET-ALM ParamInfo Cirbkr SET-ALMFuse SET-ALM Alias FuseLVD SET-ALM Batt SET-ALMComp PIN OEMAPC OFFMX28B-1200 Product Manual Rect 1ofN Alm m+ Test Relay Batt Disc Alm m+ 48V Fuse 1 Alm LVD1 LVD2MX28B-1200 Product Manual MX28B-1200 Product Manual