APC MX28B-2400, MX28B-1200 manual Test Relay

Page 48

MX28B-1200 PRODUCT MANUAL

Revision B

 

(Table 6-1. Parameter Locations, Descriptions, and Default Values)

 

 

 

 

 

PARAMETER

 

DESCRIPTION

DISPLAY SCREENS /

 

 

 

DEFAULT SETTINGS

Test Relay 1 {1}

 

Setting this parameter to “ON” energizes Relay 1 and turns

Test Relay 1

m+

[SYSTEM/DIAG]

 

on the “ALM1” LED on the control unit front panel.

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test Relay 6 {1}

 

Setting this parameter to “ON” energizes Relay 6 and turns

Test Relay 6

m+

[SYSTEM/DIAG]

 

on the “ALM6” LED on the control unit front panel.

OFF

 

 

 

 

 

 

 

 

 

 

Test Minor Relay {1}

 

Setting this parameter to “ON” energizes the Minor Relay

Test Min Rly

m+

[SYSTEM/DIAG]

 

and turns on the “MIN” LED on the control unit front panel.

OFF

 

 

 

 

 

 

 

 

Test Major Relay {1}

 

Setting this parameter to “ON” de-energizes the Major Relay

Test Maj Rly

m+

[SYSTEM/DIAG]

 

and turns on the “MAJ” LED on the control unit front panel.

OFF

 

 

 

 

 

 

 

 

BATTERY SETUP

 

 

 

 

 

 

 

 

 

Float Voltage {1}

 

Float voltage at 25°C battery temperature.

Batt Float

m+

[BATT/PARAM]

 

 

-54.00 V

 

 

 

 

 

 

 

Maximum Recharge Current

{1}

Maximum battery recharge current (the system limits the

Batt Max Rech m+

[BATT/PARAM]

 

charging current to this programmable value).

12 A

 

 

 

 

 

 

 

 

Compensation Method {1}

 

Activate “000001” or de-activate “000000” battery

Comp Method

m+

[BATT/COMP]

 

temperature compensation.

000000

 

 

 

 

 

 

 

 

 

Temperature Compensation {1}

Temperature compensation between low knee and high knee

Comp TC

m+

[BATT/COMP]

 

in mV/cell/°C. (Compensation equals zero at 25°C.)

- 3.00mV

 

 

 

 

 

 

 

Compensation High Knee {1}

The temperature compensation high knee is the point above

Comp Hknee

m+

[BATT/COMP]

 

which there is no additional battery voltage compensation for

40.0 C

 

 

further increases in temperature.

 

 

 

 

 

 

 

 

Compensation Low Knee {1}

The temperature compensation low knee is the point below

Comp Lknee

m+

[BATT/COMP]

 

which there is no additional battery voltage compensation for

0.0 C

 

 

further decreases in temperature.

 

 

 

 

 

 

 

 

Discharge Threshold {1}

 

An alarm is generated if the battery discharge current exceeds

Batt Disc Thr m+

[BATT/SET-ALM]

 

this value.

10 A

 

 

 

 

 

 

 

 

High Voltage Threshold {1}

 

An alarm is generated if the magnitude of the battery voltage

Batt HV Thr

m+

[BATT/SET-ALM]

 

rises above this value.

-58.00 V

 

 

 

 

 

 

 

 

Low Voltage Threshold {1}

 

An alarm is generated if the magnitude of the battery voltage

Batt LV Thr

m+

[BATT/SET-ALM]

 

drops below this value.

-44.00 V

 

 

 

 

 

 

 

 

High Temperature Threshold

{1}

An alarm is generated if the battery temperature exceeds this

Batt HT Thr

m+

[BATT/SET-ALM]

 

value.

70.0 C

 

 

 

 

 

 

 

 

Low Temperature Threshold

{1}

An alarm is generated if the battery temperature drops below

Batt LT Thr

m+

[BATT/SET-ALM]

 

this value.

0.0 C

 

 

 

 

 

 

 

 

42

MX28B-1200/2400

Image 48
Contents Model MX28B-1200/2400 MX28B-1200 Product Manual Revision History Revision Date DescriptionTable of Contents Product Manual Page General Information IntroductionInspection upon Receipt of Goods General Visible External DamageConcealed Damage Return of Damaged GoodsCustomer Service and Support Page Warranty Provisions Warranty ReturnsWarranty Repair or Replacement General ProvisionsMX28B-1200 Product Manual Product Overview and Technical Description DescriptionMX28B-1200 System Diagram Power Output Capacity RectifiersControl Unit AC Input Power Battery connectionsDC Distribution Environmental MechanicalCompliance Page Installation Procedures Preparation Recommended ToolsRecommended Test Equipment Equipment InspectionRoom/Locations MountingVentilation Terminal BlockMX28B-1200 Product Manual Battery Connections Battery Disconnect Connecting the CablesCable Sizing Considerations Rectifier Installation Multiple Frame Assembly Power Bus ConnectionsControl Wiring Extension Multi-Bay Wiring Diagram MX28B-1200 Product Manual Alarm Connections Alarm Interface PC BoardExternal Alarm Inputs External Alarm Input DefinitionExternal Alarm Input Connections Alarm Outputs Alarm Terminal Output Designation User Alarm Notes NO-NC-C Plug-in Circuit BreakersFuse APC Part Rating Power Distribution Fuse Load Connections 10 Fuse Bay ConnectionsBattery Temperature Probe Installation Apply AC PowerStatus Alarms System Modules Batt PIN OEM Full System Power UpPage SETUP, ADJUSTMENTS, and Operation User InterfaceAlarm Output Relays Parameter Locations, Descriptions, and Default ValuesMX28B-1200 Product Manual Alarms Setup PINStatus System SET-ALMDate OUT-RLY RLY-MAPAlias IN-RLY RLY-MAPModules Rect SET-ALM ParamInfo Cirbkr SET-ALMFuse SET-ALM Alias FuseLVD SET-ALM Batt SET-ALMComp PIN OEMAPC OFFMX28B-1200 Product Manual Rect 1ofN Alm m+ Test Relay Batt Disc Alm m+ 48V Fuse 1 Alm LVD1 LVD2MX28B-1200 Product Manual MX28B-1200 Product Manual