Revision B |
|
5.1.7 Ventilation
The rectifiers have fans that provide front to rear airflow for internal cooling. The MX28B housing should mounted such that there is free airflow to the front and top of the unit. [Refer to Section 4.8 for environmental characteristics.]
5.2 AC Service and Ground Connections
***** WARNING *****
Ensure that all of the dc and external ac circuit breakers are in the OFF position prior to connecting service to the power plant. Confirm that all voltages have been removed including any battery sources before proceeding.
The MX28B dc power plant requires the supply of 208/220/240V ac, single- phase, 50/60 Hz power through individual external
The ac input enclosure, located at the top rear of the MX28B housing, is provided with nine ¼
AC Input
Enclosure
Access
Opening
Vertical channel for AC wiring
Figure 5-2 AC Wiring Access
AC wiring passing through the conduit will be routed through the access opening in the ac input enclosure into the vertical wiring channel where safety ground bar and rectifier input terminal blocks are located. The terminal block(s) is labeled as Rectifier 1 through Rectifier 4 with each position having inputs designated “L1” and “L2” for connection of the two ac wires (Figure
The suggested wire size is #10 AWG rated at 90°C or higher; however, the ambient temperature and number of wires in a
Figure 5-3 AC
Terminal Block
15