APC MX28B-1200, MX28B-2400 manual Power Output Capacity, Rectifiers, Control Unit

Page 15

Revision B

MX28B-1200 PRODUCT MANUAL

4.2Power Output Capacity

A single power box frame consists of six rectifier shelves, each shelf accommodating up to four hot-plug, 50 amp rectifiers. A completely configured power frame with 24 rectifiers is rated at 1200 amps. Each additional power frame will add up to 1200 amps for a maximum total of 2400 amps using 48 rectifiers. A single master control unit in the first power frame provides control and monitoring for the entire system.

4.3Rectifiers

The rectifiers are APC Model MRF28H54BV with specifications as follows:

Input Voltage:

176-264V ac (230V ac nominal) @ 45-66 Hz

• Input Current per Rectifier:

13.9 Amps @ 230V ac

Apparent Power Factor:

99% Typical, 98% Minimum

Output Voltage:

54.5V dc

Overvoltage Protection:

Set at 59.5V dc

• Output Current per Rectifier:

50 Amps Minimum Continuous

• Power Output per Rectifier:

2800W Continuous, Vin > 198V ac

Efficiency:

91% Typical

Cooling:

Fan cooled, front to rear airflow

Ambient Temperature:

-25°C to 65°C Operational

4.4Control Unit

The microprocessor-based power system control unit is 1U high (1.75”) and provides control and monitoring functions. Features implemented are:

32-character alphanumeric display (2 lines by 16 characters)

LED alarm and status indicators

Standard voltage and battery charging control

Battery temperature compensation (optional temperature probe)

Monitoring of up to 18 shelves of four rectifiers each

Individual alarm monitoring of 72 breakers

Individual alarm monitoring of ten power distribution fuses

Eight alarm / annunciation relays (Major, Minor, and six user defined) with form C contact outputs

Four external alarm inputs (either N.O. or N.C. contacts)

Control for two independent Low Voltage Disconnects (LVD’s)

MX28B-1200/2400

9

Image 15
Contents Model MX28B-1200/2400 MX28B-1200 Product Manual Revision Date Description Revision HistoryTable of Contents Product Manual Page Visible External Damage General InformationIntroduction Inspection upon Receipt of Goods GeneralReturn of Damaged Goods Concealed DamageCustomer Service and Support Page General Provisions Warranty ProvisionsWarranty Returns Warranty Repair or ReplacementMX28B-1200 Product Manual Description Product Overview and Technical DescriptionMX28B-1200 System Diagram Power Output Capacity RectifiersControl Unit AC Input Power Battery connectionsDC Distribution Environmental MechanicalCompliance Page Equipment Inspection Installation ProceduresPreparation Recommended Tools Recommended Test EquipmentMounting Room/LocationsTerminal Block VentilationMX28B-1200 Product Manual Battery Connections Battery Disconnect Connecting the CablesCable Sizing Considerations Multiple Frame Assembly Power Bus Connections Rectifier InstallationControl Wiring Extension Multi-Bay Wiring Diagram MX28B-1200 Product Manual Alarm Interface PC Board Alarm ConnectionsExternal Alarm Inputs External Alarm Input DefinitionExternal Alarm Input Connections Alarm Outputs Plug-in Circuit Breakers Alarm Terminal Output Designation User Alarm Notes NO-NC-CFuse APC Part Rating 10 Fuse Bay Connections Power Distribution Fuse Load ConnectionsApply AC Power Battery Temperature Probe InstallationFull System Power Up Status Alarms System Modules Batt PIN OEMPage User Interface SETUP, ADJUSTMENTS, and OperationParameter Locations, Descriptions, and Default Values Alarm Output RelaysMX28B-1200 Product Manual System SET-ALM AlarmsSetup PIN StatusIN-RLY RLY-MAP DateOUT-RLY RLY-MAP AliasCirbkr SET-ALM Modules Rect SET-ALMParam InfoAlias Fuse Fuse SET-ALMPIN OEM LVD SET-ALMBatt SET-ALM CompOFF APCMX28B-1200 Product Manual Rect 1ofN Alm m+ Test Relay Batt Disc Alm m+ 48V Fuse 1 Alm LVD2 LVD1MX28B-1200 Product Manual MX28B-1200 Product Manual