Revision B |
| PRODUCT MANUAL |
| ||
(Table |
| ||||
|
|
|
|
| |
PARAMETER |
| DESCRIPTION |
| DISPLAY SCREENS / | |
|
|
|
| DEFAULT SETTINGS | |
System Low Temperature | {1} | The control unit temperature is below the low temperature |
| Sys LT Alm | m+ |
| threshold. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
| |
Rectifier Configuration {1} | The rectifier configuration differs from its stored |
| Rect Cfg Alm | m+ | |
| configuration. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
| |
Rectifier Fail |
| Rectifier Fail |
| Rect 1ofN Alm m+ | |
| alarm condition. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
| |
Rectifier Fail |
| Rectifier Fail |
| Rect 2ofN Alm m+ | |
| least one alarm condition each. |
| Major |
| |
|
|
|
|
| |
|
|
|
|
|
|
Hardware System Voltage | {2} | This alarm indicates there is a hardware failure in the system |
| Hw Sys V Alm | m+ |
| voltage monitoring function. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
| |
Hardware Battery Current | {2} | This alarm indicates there is a hardware failure in the battery |
| Hw Batt C Alm m+ | |
| current monitoring function. |
| Minor |
| |
|
|
|
|
| |
|
|
|
| ||
Hardware Battery Temperature {2} | This alarm indicates there is a hardware failure in the battery |
| Hw Batt T Alm m+ | ||
| temperature monitoring function. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
| |
Hardware System Temperature {2} | This alarm indicates there is a hardware failure in the system |
| Hw Sys T Alm | m+ | |
| temperature monitoring function. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
|
|
Hardware LVD1 {2} |
| This alarm indicates there is a conflict between the |
| Hw LVD1 Alm | m+ |
| commanded and sensed positions of the LVD1. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
|
|
Hardware LVD2 {2} |
| This alarm indicates there is a conflict between the |
| Hw LVD2 Alm | m+ |
| commanded and sensed positions of the LVD2. |
| Minor |
| |
|
|
|
|
| |
|
|
|
|
| |
SYSTEM ALARMS DISPLAY |
|
|
|
| |
|
|
|
|
|
|
Alarms Item 1 |
| Display of up to 16 active alarms (a typical alarm screen is |
| Alarm Item 1 | + |
[ALARMS] |
| shown). |
| Batt LV Alm On m | |
|
|
|
| ||
|
|
|
|
|
|
• |
| • |
| • |
|
• |
| • |
| • |
|
• |
| • |
| • |
|
|
|
|
|
|
|
Alarms Item 16 |
| Display of up to 16 active alarms (a typical alarm screen is |
| Alarm Item 16 | + |
[ALARMS] |
| shown). |
|
|
|
|
|
|
|
|
|
SYSTEM DIAGNOSTICS |
|
|
|
|
|
|
|
|
|
|
|
Store Configuration {1} |
| Setting this parameter to “Enable” will cause the current |
| Store Cfg | m+ |
[SYSTEM/DIAG] |
| rectifier configuration to be stored (the display toggles back |
| Disable |
|
|
| to “Disable” after entry). |
|
| |
|
|
|
|
| |
|
|
|
|
|
|
Lamp Test {1} |
| Setting Lamp Test to “ON” will turn on the “MAJOR”, |
| Lamp Test | m+ |
[SYSTEM/DIAG] |
| “MINOR”, “NORMAL”, “MAJ”, and “MIN” LEDs on the |
| OFF |
|
|
| control unit front panel. |
|
| |
|
|
|
|
| |
|
|
|
|
| |
Test Relay Enable {1} |
| This parameter must be set to “Enable” to permit the eight |
| Test Relay En m+ | |
[SYSTEM/DIAG] |
| output relays to be manually tested; otherwise, the state of the | Disable |
| |
|
| relays will be per system conditions. |
|
| |
|
|
|
|
| |
|
|
|
|
|
|
41 |