APC AP9607 manual Multiple SmartSlot Installation

Page 17

Multiple SmartSlot Installation continued

If your UPS has If your UPS has exactly one SmartSlot accessory slot, use

one SmartSlot this accessory slot for the SmartSlot device with the lowest

accessory slot priority. Install SmartSlot devices with higher priority in an Expansion Chassis (AP9600) or Triple Chassis (AP9604 — see “Installation in the APC Triple Chassis” on this page).

If you are using a Symmetra PowerArray, see “Installation in the Symmetra PowerArray” on page 14.

Installation in To install SmartSlot devices in the APC Triple Chassis

the APC Triple (AP9604), note that the slots are numbered on the rear

Chassispanel. The following figure shows the rear panel of the Triple Chassis with the PowerNet SNMP Adapter installed in slot #3, Call-UPS II in slot #2, and the Interface Expander in slot #1. (In this scenario, Measure-UPSII could be installed in the accessory slot of the UPS.)

Continued on next page

13

Image 17
Contents Interface Expander Thank You Contents Connection procedure Connecting the Interface Expander Introduction On next Hardware Software Requirements Part Number By the Interface Expander. When ordering a cable, provideProduct Description Status Description Communication Types Simple Signaling Smart SignalingKey Concepts UPS can provide simple signaling, we strongly recommend PowerChute plus, configured for smart signaling, to moniPowerChute plus Expander use simple signaling with PowerChute orUPS and continue with the installation, including Signaling. Use either one of these proceduresReboot of the system Run PowerChute plus and connect to the UPSLess of whether the UPS is on battery. The Interface Interface Expander generates a Low Battery signalExpander generates a Low Battery signal under certain Other conditions according to the configured shutdownKey Concepts Multiple SmartSlot Installation Multiple SmartSlot Installation Multiple SmartSlot Installation Installation Slot. Slide the Interface Expander all the way into Orient the Interface Expander to fit the accessorySlot until the front panel is flush with the back Panel of the UPS or deviceConnecting to Protected Devices Described in Connection procedure on Configuring the Interface Expander Firmed shutdown mode when set up for simple signaling Some versions of PowerChute plus do not support ConPowerChute plus installation directory. To find out Whether your version of PowerChute plus supports ConUPS before all connected servers have signaled shut If power returns before any connected server has signaledUPS battery is exhausted, shutting down the UPS after Low Battery Signal Time has elapsedPower is restored, or until the battery is exhausted. If Expander allows the UPS to run on battery until utilityInterface Expander detects a UPS Low Battery condition, it Equal to the Low Battery Signal Time and then shuts downTesting Interface Expander Warranty Information Purpose. Some jurisdictions do not permit limitation or Claims by third parties, or otherwise. This warranty givesExclusion of implied warranties therefore, the aforesaid Specifically, APC is not liable for any costs, such as lostTroubleshooting Problem Possible Cause Solution Troubleshooting on page 26, or if the problem For problems not covered in the troubleshooting chart seePersists, follow this procedure Lem. a technician will help solve the problem overLife-Support Policy Specifications Assignments Interface Expander SpecificationIndex Index Y, Z Page Cil Directives Standards to Which Application of CounConformity is DeclaredW. a p c c . c o m