Honeywell Q7055A user manual L1 Bus Termination, XD508 compatible bus termination enabled

Page 22

BUILDING NETWORK ADAPTER BNA-1C/2CS/2DN

XD508 compatible; bus termination enabled

XD508 compatible switch position for C-Busses equipped only with XL500 family controllers with bus termination enabled. This switch position must be used if the BNA device is installed at the end of such a C-Bus.

5.4L1 Bus Termination

This section applies to BNA 2DN devices only.

The required L1 bus EOLRs (End of Line Resistors) can be connected externally onto each CH1 / CH2 connector.

When the L1 bus uses 18 gage, twisted pair, non- shielded wire, the ends of the line should be terminated with a 62 ±10% 0,5 W carbon resistor between each wire and ground.

When the L1 bus uses 24 gage, dedicated solid copper pair, standard balanced telephone cable, the ends of the line should be terminated with a 100 ±5% 0,5 W carbon resistor between each wire and ground.

For further information regarding L1 bus termination, please refer to Honeywell DeltaNet R7044 EXCEL PLUS CONTROLLER Application Guide 74-2548, Rev.2/93.

22

EN1B-0198GE51 R0801

Image 22
Contents Q7055A Technical Data Table of Contents Cables and Connectors Tips & Tricks FAQs GlossaryAbout BNA Building Network Adapter BNA-1C/2CS/2DN Building Network Adapter BNA-1C/2CS/2DN Front Side ResetLocation of Parts and Controls ModeCol Ch2 PowerCh1 HeartbeatCh1/Ch2 Bus Termination Switches Rear Side12 RS232 10 Ch111 AC/DC 14 10BaseTBefore Installation Pieces ItemWA RN I NG BNA Operating Positions Single DeviceStacked Devices Wall MountingPut the BNA-adapter with the topside down on the desk Figure Building Network Adapter BNA-1C/2CS/2DN Power Connection ConnectionsBus Termination Switch Field Bus Connection Ch1 / Ch2FS90-Bus connections DisabledNormal XD508 compatible bus terminationXD508 compatible bus termination enabled L1 Bus TerminationBNA Bootloader Startup BehaviorRED Switching the Operating Mode Operating ModesBuilding Network Adapter BNA-1C/2CS/2DN Switching BNA Operating Mode Device Setup Command Description on Basic network parameters CA UT I on Command Description Help or ? Np Basic network parametersDc Download configuration Building Network Adapter BNA-1C/2CS/2DN Building Network Adapter BNA-1C/2CS/2DN Parameters may be wrong is acceptable Load Load executablePing ping Ver Show installed softwareRun Execute installed software Um User managementBuilding Network Adapter BNA-1C/2CS/2DN User AdminPriv Login Login as different user Whoami Who amBuilding Network Adapter BNA-1C/2CS/2DN Cables and Connectors DB9F Null Modem Cable2shows how to configure a Null Modem Cable DB9F Ethernet Connectors 1 RJ45 ConnectorPin Number Signal Name Connecting a BNA to a HubConnecting a BNA to a Workstation Straight through pinning for BNA to Ethernet Hub connectionsAUI Connector Crossover pinning for BNA to workstation direct- connectionsGND BNA bootloader np display followed by Enter Tips & TricksFAQs Glossary Building Network Adapter BNA-1C/2CS/2DN Page Honeywell