www.axxessid.com
Installation & User Guide
Proximity Readers
Honeywell proximity readers have been designed to be installed for use with access control systems. The following instructions outline the connections between the reader and the AX200 access control system as well as the software configurations that need to be carried out in order to make the system ready to operate.
How to connect the reader to the host
The reader is supplied with an
cable. To connect the reader to the AX200 system, perform the following steps:
1.If there is a connector on the end of the cable (used during manufacture for testing purposes), cut it off. Prepare the reader cable by cutting the cable jacket back 1.25 inches and strip the wires 0.5 inch.
2.The reader is connected directly to the AX100 controller. The table below shows the connections on the AX100 controller and the corresponding wires on the Honeywell proximity reader.
Colour | AX100 |
Red | 12V |
Black | 0V |
White | D1 |
Green | D0 |
Brown | LED |
When using a separate power supply for the reader, power supply and the AX100 must have a common ground.
3.Do not connect the Tamper (purple) lead to the AX100.
4.Trim and cover all conductors that are not used.
Software Configuration
Once the reader & the AX100 controller have been connected to the AX200 unit you should be able to see it on the controllers menu on the right hand side of the main screen. In order to program a valid card with the ability to have access through a Honeywell proximity reader you need to choose the correct format.
1.On the main screen click on the Format & Statistics.
2.Under the Card Matching tab press “Select Reader”
3.Choose the appropriate reader from the list and present the card to the reader
4.The software will automatically display the card number, Facility Code and the possible card formats.
AX200 Installation & User Guide – July 2007 | 1 1 5 |