Tripp Lite SR18UB owner manual Leveling, Floor, Ground Connection

Page 5

4.Enclosure Installation (continued)

4.5Leveling

WARNING: Level the enclosure before attempting to install equipment. Install the enclosure in a structurally sound area with a level floor that is able to bear the weight of the enclosure, all equipment that will be installed in the enclosure and any other enclosures and/or equipment that will be installed nearby.

1After the enclosure has been moved to the installation location, use a carpenter's level to check the slope of the floor. If the floor slopes more than 1%, choose an alternate installation site.

1

2Use a 14 mm open-end wrench to lower each leveler A until it reaches the floor. (There are 4 levelers, 2 at the front and 2 at the rear.) Make sure each leveler contacts the floor solidly. Note: Lower a leveler by turning it clockwise; raise a leveler by turning it counter-clockwise.

FLOOR

A

2

3After lowering each leveler, use the carpenter's level to confirm that the enclosure is level in all directions. Adjust the levelers as required until the enclosure is level.

3

4.6 Ground Connection

All parts of the enclosure are grounded to the frame of the enclosure.

Grounding studs have been provided in all four corners of the enclosure to allow for grounding in any configuration (including front or back door reversals).

Grounding holes are also provided on top and bottom corners of both front and back doors to accommodate any configuration.

To ground the enclosure simply connect the two quick-disconnect grounding wires, one to the hole provided on the inside of either the front or back door and the other to the stud provided in any corner of the enclosure. Connect your facility’s earth ground connection to the grounding stud not used by door connections, using an 8 AWG (3.264 mm) wire.

Warning: Attach each enclosure to earth ground separately. Do not use the enclosure without an earth ground connection.

EARTH GROUND

5

Image 5
Contents 18U SmartRack Enclosure Overview Important Safety InstructionsFeature Identification Enclosure Installation Ground Connection LevelingFloor Adjusting Mounting Rail Depth Enclosure ConfigurationDoor Locks Reversing the DoorsSpecifications Equipment InstallationWarranty and Warranty Registration Storage and ServiceService StorageManual del propietario Configuración del rackGuarde Estas Instrucciones Instrucciones de seguridad importantesGeneralidades Identificación de las características Preparación Instalación del rackInstalación de Ruedas y Niveladores UbicaciónNivelación del rack Instalación del rack continuaciónSuelo Conexión a tierraCerraduras de las puertas Configuración del rackCómo invertir las puertas Rieles de montajeEspecificaciones Instalación de equiposGarantía Almacenamiento y servicioAlmacenamiento ServicioManuel de l’utilisateur Configuration de l’armoireConservez CES Instructions Consignes de sécurité importantesPrésentation Identification des pièces de l’armoire Avertissements avant l’installation Installation de l’armoireInstallation des roulettes et des vérins de calage PréparationMise à niveau Installation de l’armoire suiteSOL Mise à la terreVerrous des portes Configuration de l’armoireInverser le sens des portes Rails de montageSpécifications techniques Installation de l’équipementGarantie Entreposage et entretienEntreposage Entretien